Set the value in accordance with the 
boiler 

manufacturer‟s 

recommendations 

12.6

 

Fuel shortage detection time n5 

This is the time after which the regulator will 
produce the fuel shortage alarm.  

 

If  the  regulator  produces  the  “No 

fuel”  alarm  too  fast,  increase  the 
value of this parameter. 

Recommended  settings  of  the  n5  parameter 

depending  on  the  method  of  detecting  fuel 
shortage: 

Detection method 

n5 value 

1 – boiler sensor 

20min 

2 – emission 

sensor 

10min 

Methods of detection are specified in point 
12.21. 

12.7

 

Screen brightness n6 

Increases  or  decreases  the  brightness  of 

display backlight. 

12.8

 

Fan revolutions’ reduction 

temperature n7 

This parameter is applicable only if the boiler 
regulation  mode 

  =  1  –  CLASSIC  is 

enabled.  After  the  boiler  reaches  the 

boiler 

preset  temperature  –  n7

,  the  fan  starts 

reducing its revolutions until the boiler preset 

temperature is reached. By default n7 = 5

C.

  

 

Drawing 14 Fan revolutions‟ reduction with classic 
regulation 

12.9

 

Central heating pump down-time 

by thermostat n8 

This  parameter  determines  the  central 
heating  pump  down-time  after  it  is  blocked 
by  disconnected  room  thermostat,  at  the 
moment 

of 

reaching 

preset 

room 

temperature  (point  11.10).  As  a  result  of 
blocking  the  central  heating  pump,  the 
temperature  in  the  heated  rooms  will  drop, 
and  the  boiler  will  reach  the  preset 
temperature  faster  and  switch  to  the 
SUPERVISION  mode.  Yet,  too  long  a 
blockade  of  the  central  heating  pump  will 
cause  the  system  to  cool  down,  which  is 
disadvantageous  for  maintaining  the  room 
temperature  at  constant  level.    The  heating 
medium accumulated in the system has high 
thermal  inertia,  and  heating  it  after  the 
thermostat contacts are shorted can take too 
long.  Thus,  it  is  not  recommended  to  set 
excessively long central heating pump down-
times. After the 

central heating pump down-

time  by  thermostat 

(service  parameter  n8), 

the  regulator  will  enable  it  for  a  constant, 
pre-programmed time of 30 s. 

12.10

 

Fuel shortage detection methods 

n9 

This  parameter  determines  the  method  of 
detecting fuel shortage. If: 
n9  =  1,  fuel  shortage  is  detected  on  the 
basis  of  the  boiler  temperature  readings  T1, 
point 14.1,  
n9  =  2,  fuel  shortage  is  detected  on  the 
basis of emission sensor T3 readings. Do not 
set n9=2 if emission sensor is disconnected.  

12.11

 

Lowering the preset boiler 

temperature r0 

Settings  of  lowering  the  preset  boiler 
temperature r0 are described in point 11.10. 

12.12

 

Hot utility water tank hysteresis 

r1 

This  is  a  drop  of  temperature  below  which 
the  hot  utility  water  pump  is  restarted  in 
order to fill the hot utility water tank.  
 

 

After  setting  a  low  value,  the  hot 
utility  water  pump  will  start  faster, 
yet  this  is  disadvantageous  due  to 
frequent activation of the pump. 

 
 
 

Summary of Contents for ecoMAX 200 W

Page 1: ...oiler regulator ecoMAX 200 W FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE 1 3 APPLICABLE TO SOFTWARE 10 034 10 035 10 036 2010 04 14 Dzia Zintegrowanego Systemu Zarz dzania...

Page 2: ......

Page 3: ...1 CONNECTING TEMPERATURE LIMITER STB 20 11 12 CONNECTING ADDITIONAL THERMAL PROTECTION 20 11 13 SMOOTH FAN START 20 12 Service settings 21 12 1 CENTRAL HEATING PUMP ACTIVATION TEMPERATURE N0 21 12 2 B...

Page 4: ...erature limiter Therefore it cannot be used instead of a safety temperature limiter The value of the programmable parameters should be selected appropriately to the parameters of the given boiler and...

Page 5: ...rtable temperature in the heated rooms 3 Information about documentation The regulator manual is a supplement for the boiler manual In particular except for this manual the boiler manual should also b...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX 200 W...

Page 8: ...ng the preset boiler temperature due to hot utility water heating 10 signal decreasing the preset boiler temperature due to operation of the room thermostat 11 service menu symbol 12 hot utility water...

Page 9: ...l the arrow is in the boiler regulation mode position Use or buttons to set value The method is based on the T1 boiler indication and consists in decreasing of the airflow power from Maximum revolutio...

Page 10: ...the PID EMISSION mode Moreover after equipping the regulator with an emission sensor it is possible to enable very fast detection of fuel shortage This provides additional saving of heat energy resul...

Page 11: ...temperature exceeds the preset boiler temperature by 10 C In the SUPERVISION mode the fan is enabled cyclically for short periods in order to prevent the fire from going out and to remove accumulated...

Page 12: ...e regulator outputs The window shown at Drawing 5 appears and the central heating pump symbol flashes first Drawing 5 Manual control Press START and STOP to change the status of the given output START...

Page 13: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX 200 W...

Page 14: ...d by the regulator where 1 ecoMAX 200 regulator 2 central heating pump 3 hot utility water pump 4 fan 5 room thermostat 6 hot utility water tank 7 central heating system 8 chimney duct 9 boiler T1 boi...

Page 15: ...of 15 60 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 11 Regulator installation 11 1 Environmental conditions Due to the risk of ex...

Page 16: ...ermal conditions and safety issues a safe distance between active parts of the terminals and the conductive metal elements of the enclosure must be kept Drawing 10 Metal elements of the regulator encl...

Page 17: ...d with an arrow Drawing 12 Diagram of electric connections with external devices where T1 boiler temperature sensors type CT4 T2 hot utility water temperature sensors type CT4 T3 emission temperature...

Page 18: ...at least 0 5mm2 Total length of the sensor leads cannot exceed 15 m The boiler temperature sensor CT4 should be fitted in the thermometric pipe situated in the boiler shell Hot utility water temperatu...

Page 19: ...be filled via hot utility water pump select the hot utility water pump operation mode acc to point 7 9 11 10 Connecting room thermostat To make the boiler more economical and the temperature in the h...

Page 20: ...l order It cuts off the fan power supply Sensor of the additional thermal protection which operates on low safe voltage should be placed in the thermometric pipe of the water jacket You should provide...

Page 21: ...eating pump is activated This protects the boiler against retting caused by its being cooled down by hot water returning from the system Disabling the central heating pump on its own does not guarante...

Page 22: ...e in the heated rooms will drop and the boiler will reach the preset temperature faster and switch to the SUPERVISION mode Yet too long a blockade of the central heating pump will cause the system to...

Page 23: ...the hot utility water pump when the central heating pump is disabled In order to cool the boiler down operation of the hot utility water pump can be extended by the time r4 Extending hot utility wate...

Page 24: ...he cases of power supply failure the regulator will resume the operation mode in which it was before the failure 13 Firmware WARNING Values of the following parameters can be modified only by qualifie...

Page 25: ...threshold Thanks to this a momentary exceeding of the boiler temperature will not cause stoppage of the boiler Before the boiler reaches the P0 temperature the regulator will attempt to drop the exces...

Page 26: ...temperature limiter STB input jumper is on terminals 1 2 the jumper should be placed only if no temperature limiter is connected check if the additional thermal protection sensor input jumper is on te...

Page 27: ......

Reviews: