The regulator is started by pushing the mains 
switch  (4)  Drawing  1.  First,  an  information 
window  with  the  software  version  appears, 
then the regulator displays the main window.  

7.4

 

Firing up – activation of airflow  

In order to fire the boiler up, you should put 
fire  under  the  fuel,  in  accordance  with  the 
boiler  documentation,  close  the  boiler  door 
and  activate  airflow  by  pushing  the  START 
button.  The  fan  will  be  activated.  Pushing 
STOP  turns  the  fan  and  the  regulation 
process off.  

7.5

 

Presetting boiler temperature 

The  boiler  temperature  can  be  preset  by 
pushing  the  F  button  in  the  main  menu.  A 
signalling 

arrow 

next 

to 

the 

sign 

„Temperature  setting”  is  lit,  and  the  boiler 
preset temperature value in the upper part of 
the  thermometer  flashes.  START  and  STOP 
buttons  are  used  to  increase  and  decrease 
the preset boiler temperature respectively. 

7.6

 

Presetting hot utility water 

temperature 

The  hot  utility  water  temperature  can  be 
preset  by  pushing  the  F  button  in  the  main 
menu  twice.  A  signalling  arrow  next  to  the 
sign „Temperature setting” is lit, and the hot 
utility water preset temperature value in the 
upper  part  of  the  thermometer  flashes. 
START  and  STOP  buttons  are  used  to 
increase  and  decrease  the  preset  hot  utility 
water temperature respectively. 

7.7

 

Combustion regulation methods  

The  regulator  features  three  selectable 
methods  of  regulating  the  combustion 
process. 

CLASSIC regulation (regulation mode 1)

  

In  order  to  enable  the  CLASSIC  mode  of 
boiler  regulations,  set  the 

boiler  regulation 

mode 

 

to value 1. In order to do so, press 

the  F  button  in  the  main  window  until  the 
arrow  is  in  the 

boiler  regulation  mode 

position. Use „+” or „-" buttons to set value  

The  method  is  based  on  the  T1  boiler 
indication,  and  consists  in  decreasing  of  the 
airflow power from 

Maximum revolutions 

 

to 

Minimum

 

revolutions 

 while achieving 

the  preset  boiler  temperature.  Revolutions 
start  to  be  reduced  at  5°C  (service 
parameter  n7)  before  the  preset  boiler 
temperature.  After  achieving  the  preset 
boiler  temperature,  the  SUPERVISION  mode 
is activated, where blow-offs are performed. 

Before enabling  this mode for the first time, 
it  is  recommended  to  program  the  regulator 
in accordance with point 11.9.  

PID regulation (regulation mode 2)

 

After  setting  the  parameter 

boiler  regulation 

mode = 

2. 

This  method  is  based  on  boiler  temperature 
indications  T1,  it  consists  in  constant, 
smooth  modulation  of  the  fan  revolutions  in 
order  to  stabilize  the  preset  boiler 
temperature.  The  regulator  itself  selects  the 
airflow  power  in  such  a  way  that  the  boiler 
generated  minimum  amount  of  heat 
necessary to satisfy the heat demand of the 
building.  Transition  to  the  SUPERVISION 
mode  is  rare  and  it  happens  during  lack  of 
heat demand. 

Before enabling  this mode for the first time, 
it  is  recommended  to  program  the  regulator 
in accordance with point 11.9.  

PID  EMISSION  regulation  (regulation 
mode 3) – new! 

 

Three modes of combustion control 
are available: 1 - CLASSIC, 2 - PID, 
3 – PID SALINES point 7.7. 

 

 

If the hot utility water temperature 
sensor  is  not  connected,  it  is  not 
possible  to  preset  the  hot  utility 
water temperature.

 

 

Caution: The combustion regulation 
methods  described  below  will 
properly  regulate  the  combustion 
process,  as  long  as  the  boiler  is 
operated 

in 

accordance 

with 

recommendations  of  the  boiler 
manufacturer.  You  should  pay 
special  attention  to  the  place  of 
setting fire during firing up! 

 

Summary of Contents for ecoMAX 200 W

Page 1: ...oiler regulator ecoMAX 200 W FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE 1 3 APPLICABLE TO SOFTWARE 10 034 10 035 10 036 2010 04 14 Dzia Zintegrowanego Systemu Zarz dzania...

Page 2: ......

Page 3: ...1 CONNECTING TEMPERATURE LIMITER STB 20 11 12 CONNECTING ADDITIONAL THERMAL PROTECTION 20 11 13 SMOOTH FAN START 20 12 Service settings 21 12 1 CENTRAL HEATING PUMP ACTIVATION TEMPERATURE N0 21 12 2 B...

Page 4: ...erature limiter Therefore it cannot be used instead of a safety temperature limiter The value of the programmable parameters should be selected appropriately to the parameters of the given boiler and...

Page 5: ...rtable temperature in the heated rooms 3 Information about documentation The regulator manual is a supplement for the boiler manual In particular except for this manual the boiler manual should also b...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX 200 W...

Page 8: ...ng the preset boiler temperature due to hot utility water heating 10 signal decreasing the preset boiler temperature due to operation of the room thermostat 11 service menu symbol 12 hot utility water...

Page 9: ...l the arrow is in the boiler regulation mode position Use or buttons to set value The method is based on the T1 boiler indication and consists in decreasing of the airflow power from Maximum revolutio...

Page 10: ...the PID EMISSION mode Moreover after equipping the regulator with an emission sensor it is possible to enable very fast detection of fuel shortage This provides additional saving of heat energy resul...

Page 11: ...temperature exceeds the preset boiler temperature by 10 C In the SUPERVISION mode the fan is enabled cyclically for short periods in order to prevent the fire from going out and to remove accumulated...

Page 12: ...e regulator outputs The window shown at Drawing 5 appears and the central heating pump symbol flashes first Drawing 5 Manual control Press START and STOP to change the status of the given output START...

Page 13: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX 200 W...

Page 14: ...d by the regulator where 1 ecoMAX 200 regulator 2 central heating pump 3 hot utility water pump 4 fan 5 room thermostat 6 hot utility water tank 7 central heating system 8 chimney duct 9 boiler T1 boi...

Page 15: ...of 15 60 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 11 Regulator installation 11 1 Environmental conditions Due to the risk of ex...

Page 16: ...ermal conditions and safety issues a safe distance between active parts of the terminals and the conductive metal elements of the enclosure must be kept Drawing 10 Metal elements of the regulator encl...

Page 17: ...d with an arrow Drawing 12 Diagram of electric connections with external devices where T1 boiler temperature sensors type CT4 T2 hot utility water temperature sensors type CT4 T3 emission temperature...

Page 18: ...at least 0 5mm2 Total length of the sensor leads cannot exceed 15 m The boiler temperature sensor CT4 should be fitted in the thermometric pipe situated in the boiler shell Hot utility water temperatu...

Page 19: ...be filled via hot utility water pump select the hot utility water pump operation mode acc to point 7 9 11 10 Connecting room thermostat To make the boiler more economical and the temperature in the h...

Page 20: ...l order It cuts off the fan power supply Sensor of the additional thermal protection which operates on low safe voltage should be placed in the thermometric pipe of the water jacket You should provide...

Page 21: ...eating pump is activated This protects the boiler against retting caused by its being cooled down by hot water returning from the system Disabling the central heating pump on its own does not guarante...

Page 22: ...e in the heated rooms will drop and the boiler will reach the preset temperature faster and switch to the SUPERVISION mode Yet too long a blockade of the central heating pump will cause the system to...

Page 23: ...the hot utility water pump when the central heating pump is disabled In order to cool the boiler down operation of the hot utility water pump can be extended by the time r4 Extending hot utility wate...

Page 24: ...he cases of power supply failure the regulator will resume the operation mode in which it was before the failure 13 Firmware WARNING Values of the following parameters can be modified only by qualifie...

Page 25: ...threshold Thanks to this a momentary exceeding of the boiler temperature will not cause stoppage of the boiler Before the boiler reaches the P0 temperature the regulator will attempt to drop the exces...

Page 26: ...temperature limiter STB input jumper is on terminals 1 2 the jumper should be placed only if no temperature limiter is connected check if the additional thermal protection sensor input jumper is on te...

Page 27: ......

Reviews: