Drawing 2 AL1 alarm 

No sound signal will be given. 
The way and methods of detecting fuel 
shortage are described in point 12.21. 

14.2

 

Boiler temperature sensor damage 

AL2 

This  alarm  will  be  produced  in  the  case  of 
damage  to  the  boiler  sensor,  and  after 
exceeding  its  measuring  range.  The  alarm 
sauces shut-down of the central heating and 
hot utility  water pumps, in  order to cool the 
boiler  down,  if  applicable.  A  sound  signal  is 
also activated. 
The alarm is cancelled after returning to the 
sensor  measurement  range,  and  after 
disabling  and  enabling  the  regulator  via  the 
mains switch. 
In such case, check the sensor, and possibly 
replace it.  

 

The  method  of  checking  the 
temperature  sensor  is  described  in 
point 11.8 

14.3

 

Exceeding the maximum boiler 

temperature AL3 

This alarm will occur after the boiler exceeds 
temperature  determined  by  the  factory 
parameter 

Boiler 

overheating 

alarm 

temperature P0. 

By default, this parameter is 

set  to  90

C.  In  such  case,  the  fan  is  turned 

off,  and  the  central  heating  and  hot  utility 
water pumps are activated. A sound signal is 
also  activated.  The  hot  utility  water  pump 
works  only  until  the  hot  utility  water  tank 
exceeds  the  maximum  temperature  r3 
(service  parameter).  This  protects  the  users 
against possible scalding. 
After  the  boiler  temperature  drops,  the 
regulator resumes normal operation. 

 

It  is  suggested  to  set  the  P0  value 
below  the  safety  temperature 
limiter  actuation  threshold.  Thanks 
to  this,  a  momentary  exceeding  of 
the  boiler  temperature  will  not 

cause stoppage of the boiler.

 

 

 

Before  the  boiler  reaches  the  P0 
temperature,  the  regulator  will 
attempt to drop the excessive heat 
to the hot utility water tank. If the 
hot  utility  water  tank  reaches  the 
maximum  temperature  permitted 
by the r3 parameter, the hot utility 
water  pump  is  turned  off,  and  the 
AL3 alarm is produced. 

 

 

 

Note:  placing  the  temperature 
sensor  beyond  the  boiler  water 
jacket,  e.g.  on  the  outlet  pipe,  is 
not  recommended,  as  it  can  delay 
detection of the boiler overheating. 

14.4

 

Exceeding maximum emission 

temperature 

The regulator warns the user of a danger of 
emission  temperature  sensor  damage  if  the 
emission  temperature  exceeds  450°C.  Such 
situation  can  occur  if  the  wrong  regulator 
parameters are set,  or  if the boiler door are 
left open. 
The alarm is signalled visually, by a warning 
triangle  symbol,  and  with  a  sound  –  short 
warning signals. 

15

 

Replacement of parts and 
subassemblies  

When  ordering  parts  and  subassemblies, 
please specify necessary information read off 
the  rating  plate.  It  is  best  to  give  the 
regulator serial number. If the serial number 
is  not  known,  please  specify  the  model  and 
type of the regulation, as well as the year of 
its production.  

15.1

 

Replacing mains fuse  

The mains fuse can be found in the regulator 
front panel. It protects the regulator and the 
devices  fed  by  it.    Please  use  time-delay 
fuses,  porcelain,  5x20mm,  of  nominal 
burnout current 3,15A, e.g. 

02153.15P

 made 

by LittelFuse

.

 

In order to remove the fuse, push in its 
socket with a flat-tip screwdriver and turn it 
counter clockwise. 

Summary of Contents for ecoMAX 200 W

Page 1: ...oiler regulator ecoMAX 200 W FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE 1 3 APPLICABLE TO SOFTWARE 10 034 10 035 10 036 2010 04 14 Dzia Zintegrowanego Systemu Zarz dzania...

Page 2: ......

Page 3: ...1 CONNECTING TEMPERATURE LIMITER STB 20 11 12 CONNECTING ADDITIONAL THERMAL PROTECTION 20 11 13 SMOOTH FAN START 20 12 Service settings 21 12 1 CENTRAL HEATING PUMP ACTIVATION TEMPERATURE N0 21 12 2 B...

Page 4: ...erature limiter Therefore it cannot be used instead of a safety temperature limiter The value of the programmable parameters should be selected appropriately to the parameters of the given boiler and...

Page 5: ...rtable temperature in the heated rooms 3 Information about documentation The regulator manual is a supplement for the boiler manual In particular except for this manual the boiler manual should also b...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX 200 W...

Page 8: ...ng the preset boiler temperature due to hot utility water heating 10 signal decreasing the preset boiler temperature due to operation of the room thermostat 11 service menu symbol 12 hot utility water...

Page 9: ...l the arrow is in the boiler regulation mode position Use or buttons to set value The method is based on the T1 boiler indication and consists in decreasing of the airflow power from Maximum revolutio...

Page 10: ...the PID EMISSION mode Moreover after equipping the regulator with an emission sensor it is possible to enable very fast detection of fuel shortage This provides additional saving of heat energy resul...

Page 11: ...temperature exceeds the preset boiler temperature by 10 C In the SUPERVISION mode the fan is enabled cyclically for short periods in order to prevent the fire from going out and to remove accumulated...

Page 12: ...e regulator outputs The window shown at Drawing 5 appears and the central heating pump symbol flashes first Drawing 5 Manual control Press START and STOP to change the status of the given output START...

Page 13: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX 200 W...

Page 14: ...d by the regulator where 1 ecoMAX 200 regulator 2 central heating pump 3 hot utility water pump 4 fan 5 room thermostat 6 hot utility water tank 7 central heating system 8 chimney duct 9 boiler T1 boi...

Page 15: ...of 15 60 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 11 Regulator installation 11 1 Environmental conditions Due to the risk of ex...

Page 16: ...ermal conditions and safety issues a safe distance between active parts of the terminals and the conductive metal elements of the enclosure must be kept Drawing 10 Metal elements of the regulator encl...

Page 17: ...d with an arrow Drawing 12 Diagram of electric connections with external devices where T1 boiler temperature sensors type CT4 T2 hot utility water temperature sensors type CT4 T3 emission temperature...

Page 18: ...at least 0 5mm2 Total length of the sensor leads cannot exceed 15 m The boiler temperature sensor CT4 should be fitted in the thermometric pipe situated in the boiler shell Hot utility water temperatu...

Page 19: ...be filled via hot utility water pump select the hot utility water pump operation mode acc to point 7 9 11 10 Connecting room thermostat To make the boiler more economical and the temperature in the h...

Page 20: ...l order It cuts off the fan power supply Sensor of the additional thermal protection which operates on low safe voltage should be placed in the thermometric pipe of the water jacket You should provide...

Page 21: ...eating pump is activated This protects the boiler against retting caused by its being cooled down by hot water returning from the system Disabling the central heating pump on its own does not guarante...

Page 22: ...e in the heated rooms will drop and the boiler will reach the preset temperature faster and switch to the SUPERVISION mode Yet too long a blockade of the central heating pump will cause the system to...

Page 23: ...the hot utility water pump when the central heating pump is disabled In order to cool the boiler down operation of the hot utility water pump can be extended by the time r4 Extending hot utility wate...

Page 24: ...he cases of power supply failure the regulator will resume the operation mode in which it was before the failure 13 Firmware WARNING Values of the following parameters can be modified only by qualifie...

Page 25: ...threshold Thanks to this a momentary exceeding of the boiler temperature will not cause stoppage of the boiler Before the boiler reaches the P0 temperature the regulator will attempt to drop the exces...

Page 26: ...temperature limiter STB input jumper is on terminals 1 2 the jumper should be placed only if no temperature limiter is connected check if the additional thermal protection sensor input jumper is on te...

Page 27: ......

Reviews: