15 

 

depletion  and turns  the fan off. Moreover,  it 
allows operation in  the PID-EMISSION boiler 
regulation  mode,  and  preview  of  the 
emission temperature. 
 

 

Drawing  7.    Hydraulic  diagram  with  a  thermal  buffer, 
where:  1  –  ecoMAX  200  regulator,  2  –  central  heating 
pump,    3  –  fan,    4  -  boiler,  5  -  chimney  duct,  6  – 
thermal buffer with integrated hot utility water tank, 7 – 
central heating system, 8 – external regulator of heating 
cycle,  9  –  thermostatic  valve  safeguarding  the  boiler 
return,  T1  –  boiler  temperature  sensor,  T3  –  emission 
temperature sensor. 

Brief  description  of  the  system  functioning: 
the CH pump (2) is activated after the boiler 
exceeds  the 

central  heating  pump  activation 

temperature

  (service  parameter  n0,  by 

default n0 = 40°C). After detecting shortage 
of fuel in  the boiler (4),  the CH pump (2) is 
disabled,  which  protects  the  buffer  (6) 
against heat loss. The heat cycle (7) must be 
controlled by an external regulator (8), which 
is to be purchased separately. 
Recommended settings: 
 
 
 
 

 

The  presented  hydraulic  diagram 
does  not  replace  the  central 
heating  system  design  and  it  can 
be  used  for  reference  purposes 
only. 

 
 

10

 

Storage conditions and transport 

The  regulator  cannot  be  exposed  to  direct 
effects  of  weather,  i.e.  wind  and  sunrays. 

Storage  and  transport  temperature  cannot 
exceed the scope of -15…60 °C.  
During  transport,  the  device  cannot  be 
exposed  to  vibrations  greater  than  those 
typical of normal road transport.  
 

11

 

Regulator installation 

11.1

 

Environmental conditions  

Due  to  the  risk  of  explosion  or  fire,  it  is 
prohibited  to  operate  the  regulator  in 
explosive 

gas 

and 

flammable 

dust 

atmosphere (e.g. coal dust). In such cases, it 
is  necessary  to  apply  additional  measures 
protecting  the  regulator  against  penetration 
by  flammable  dusts  and  gases  (tight  body), 
or to prevent their emergence. 
On  account  of  risk  of  shock,  the  regulator 
has  been  designed  to  be  used  in  an 
environment  marked  as  pollution  level  3, 
acc. to PN-EN 60730-1.  
Moreover,  the  regulator  cannot  be  used  in 
the presence of vapour condensation, and be 
exposed to water. 

11.2

 

Conditions of enclosing 

The  regulator  must  be  enclosed.  The 
regulator  should  be  installed  by  a  qualified 
and authorised fitter, in accordance with the 
applicable norms and regulations. 
The manufacturer bears no responsibility for 
damages  caused  by  failure  to  observe  this 
manual.  
The  regulator  cannot  be  used  as  a  stand-
alone  device.  The  temperature  of  the 
ambient  and  the  fitting  surface  cannot 
exceed the range of 0 - 50˚C. 
The  regulator  is  designed  to  be  fitted  in  a 
mounting  plate.  Proper  thermal  insulation 
between  hot  boiler  walls  and  the  regulator 
must be provided.  
A hole must be made in the mounting plate, 
in accordance with Drawing 8. 
The space required for the regulator is shown 
in Drawing 10.

 

r6=1 
n9=2 

Summary of Contents for ecoMAX 200 W

Page 1: ...oiler regulator ecoMAX 200 W FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE 1 3 APPLICABLE TO SOFTWARE 10 034 10 035 10 036 2010 04 14 Dzia Zintegrowanego Systemu Zarz dzania...

Page 2: ......

Page 3: ...1 CONNECTING TEMPERATURE LIMITER STB 20 11 12 CONNECTING ADDITIONAL THERMAL PROTECTION 20 11 13 SMOOTH FAN START 20 12 Service settings 21 12 1 CENTRAL HEATING PUMP ACTIVATION TEMPERATURE N0 21 12 2 B...

Page 4: ...erature limiter Therefore it cannot be used instead of a safety temperature limiter The value of the programmable parameters should be selected appropriately to the parameters of the given boiler and...

Page 5: ...rtable temperature in the heated rooms 3 Information about documentation The regulator manual is a supplement for the boiler manual In particular except for this manual the boiler manual should also b...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX 200 W...

Page 8: ...ng the preset boiler temperature due to hot utility water heating 10 signal decreasing the preset boiler temperature due to operation of the room thermostat 11 service menu symbol 12 hot utility water...

Page 9: ...l the arrow is in the boiler regulation mode position Use or buttons to set value The method is based on the T1 boiler indication and consists in decreasing of the airflow power from Maximum revolutio...

Page 10: ...the PID EMISSION mode Moreover after equipping the regulator with an emission sensor it is possible to enable very fast detection of fuel shortage This provides additional saving of heat energy resul...

Page 11: ...temperature exceeds the preset boiler temperature by 10 C In the SUPERVISION mode the fan is enabled cyclically for short periods in order to prevent the fire from going out and to remove accumulated...

Page 12: ...e regulator outputs The window shown at Drawing 5 appears and the central heating pump symbol flashes first Drawing 5 Manual control Press START and STOP to change the status of the given output START...

Page 13: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX 200 W...

Page 14: ...d by the regulator where 1 ecoMAX 200 regulator 2 central heating pump 3 hot utility water pump 4 fan 5 room thermostat 6 hot utility water tank 7 central heating system 8 chimney duct 9 boiler T1 boi...

Page 15: ...of 15 60 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 11 Regulator installation 11 1 Environmental conditions Due to the risk of ex...

Page 16: ...ermal conditions and safety issues a safe distance between active parts of the terminals and the conductive metal elements of the enclosure must be kept Drawing 10 Metal elements of the regulator encl...

Page 17: ...d with an arrow Drawing 12 Diagram of electric connections with external devices where T1 boiler temperature sensors type CT4 T2 hot utility water temperature sensors type CT4 T3 emission temperature...

Page 18: ...at least 0 5mm2 Total length of the sensor leads cannot exceed 15 m The boiler temperature sensor CT4 should be fitted in the thermometric pipe situated in the boiler shell Hot utility water temperatu...

Page 19: ...be filled via hot utility water pump select the hot utility water pump operation mode acc to point 7 9 11 10 Connecting room thermostat To make the boiler more economical and the temperature in the h...

Page 20: ...l order It cuts off the fan power supply Sensor of the additional thermal protection which operates on low safe voltage should be placed in the thermometric pipe of the water jacket You should provide...

Page 21: ...eating pump is activated This protects the boiler against retting caused by its being cooled down by hot water returning from the system Disabling the central heating pump on its own does not guarante...

Page 22: ...e in the heated rooms will drop and the boiler will reach the preset temperature faster and switch to the SUPERVISION mode Yet too long a blockade of the central heating pump will cause the system to...

Page 23: ...the hot utility water pump when the central heating pump is disabled In order to cool the boiler down operation of the hot utility water pump can be extended by the time r4 Extending hot utility wate...

Page 24: ...he cases of power supply failure the regulator will resume the operation mode in which it was before the failure 13 Firmware WARNING Values of the following parameters can be modified only by qualifie...

Page 25: ...threshold Thanks to this a momentary exceeding of the boiler temperature will not cause stoppage of the boiler Before the boiler reaches the P0 temperature the regulator will attempt to drop the exces...

Page 26: ...temperature limiter STB input jumper is on terminals 1 2 the jumper should be placed only if no temperature limiter is connected check if the additional thermal protection sensor input jumper is on te...

Page 27: ......

Reviews: