33
SM73
1073
Min. value for analogue output AQ1
SM74
1074
Min. value for analogue output AQ2
SM75
1075
Min. value for analogue output AQ3
SM76
1076
Min. value for analogue output AQ4
These words define the value of the software analogue
output AQx which corresponds to 0V on the physical
output. These words are modified using the instruction
RANGE(AQx,Min,Max). At starting they are selected to
0.
SM77
1077
Max. value for analogue output AQ1
SM78
1078
Max. value for analogue output AQ2
SM79
1079
Max. value for analogue output AQ3
SM80
1080
Max. value for analogue output AQ4
These words define the value of the software analogue
output AQx which corresponds to 10V on the physical
output. These words are modified using the instruction
RANGE(AQx, Min, Max). At starting they are selected
to 100.
R/W
SM81
1081
Frequency of digital analogue converter (default 55 Hz)
Defines the conversion frequency in Hz for the digital
analogue converter. Through this parameter it is
possible to change the conversion speed to obtain a
faster or more stable conversion, according to the
requirements. Allowed frequency value changes from
18 Hz (conversion slower and more precise) to 1920
Hz (conversion faster but less precise).
R/W
SM82
1082
Input AI1 conversion reference (default 0)
SM83
1083
Input AI2 conversion reference (default 0)
SM84
1084
Input AI3 conversion reference (default 0)
SM85
1085
Input AI4 conversion reference (default 0)
Defines the reference used by the digital analogue
converter to convert the analogue inputs AI. Through
these special markers, it is possible to change the
default reference (0 = AI-COM) moving it from the
analogue ground to one of the other analogue inputs,
realizing a differential reading between two AI inputs.
Allowed settings are:
R/W
0
AI-COM
1
AI1
3
AI3
2
AI2
4
AI4