29
SM32
1032
Counting increment for fast counter no. 1
SM33
1033
Counting increment for fast counter no. 2
SM34
1034
Counting increment for fast counter no. 3
SM35
1035
Counting increment for fast counter no. 4
SM36
1036
Counting increment for fast counter no. 5
Only for PL260-12AD
These words contains the number of counts which are
added to the relative counter when there is a rising or
falling transition of the counter counting input (I1, I2,
I15, I16 e I3).
R
SM37
1037
Status of digital inputs I1÷I16 for test procedure
This word defines the status for digital inputs during
test procedure (SM0.5=1). Each bit of this word
corresponds to the status of a digital input, starting
from
the
bit
less
significant
(SM37.0
I1,
SM37.15
I16). This word is zeroed automatically at
each starting.
R/W
SM38
1038
Digital inputs filter
(default 10 ms)
It is possible to filter the signals of digital inputs
selecting a delay time. If the input status changes, the
new status will be accepted only if it is stored by the
input for the selected time. Data will be accepted only
when the filter will have cancelled noises and fixed
inputs lines on stable values.
PL260 supports filters with delay time between 0 and
50 ms.
R/W