31
SM40
1040
Analogue input AI1 configuration
SM41
1041
Analogue input AI2 configuration
SM42
1042
Analogue input AI3 configuration
SM43
1043
Analogue input AI4 configuration
SM44
1044
Analogue input AI5 configuration
3
SM45
1044
Analogue input AI6 configuration
4
These special marker words define the type of sensor
connected to analogue inputs AI1...AI6 (select the
jumpers correctly to configure the inputs). At starting
these words are automatically selected as input
0..10V-10bit, AI5...AI6 as not enabled inputs.
0
Input disabled
1
Input 0÷10V (resolution 10 bit)
2
Input 0÷10V (resolution 16 bit)
3
Input 0÷1V
4
Input 0÷20mV
5
Input 0÷20mA
6
Input 4÷20mA
7
Input thermocouple type K
8
Input thermocouple type S
9
Input thermocouple type T
10
Input thermocouple type R
11
Input thermocouple type J
12
Input thermocouple type E
13
Not available
14
Input PT100
15
Input NI100
16
Input compensation PT100/NI100
(only for PT100/NI100 3 wires. Selection
allowed only for AI2 and AI3, respectively
compensation for AI1 and AI4)
17
Not available
18
Input NTC-10K
β
=3435
19
Input conversion counts
20
Input PT1000
21
Input PT500
22
Input PTC-1K
R/W
3
See par. “Setting dip-switch to select analogue intput AI5..6”
4
See par. “Setting dip-switch to select analogue intput AI5..6”