32
SM46
1046
Min. value for Analogue input AI1 linear
SM47
1047
Min. value for Analogue input AI2 linear
SM48
1048
Min. value for Analogue input AI3 linear
SM49
1049
Min. value for Analogue input AI4 linear
SM50
1050
Min. value for Analogue input AI5 linear
SM51
1051
Min. value for Analogue input AI6 linear
SM52
1052
Max. value for Analogue input AI1 linear
SM53
1053
Max. value for Analogue input AI2 linear
SM54
1054
Max. value for Analogue input AI3 linear
SM55
1055
Max. value for Analogue input AI4 linear
SM56
1056
Max. value for Analogue input AI5 linear
SM57
1057
Max. value for Analogue input AI6 linear
Select min. and max. numeric limits for the analogue
conversion of inputs AI configured as V/I (current and
tension). These words are modified using the
instruction RANGE(AIx,Min,Max). Default settings are
0 for min. value and 1000 for max. value.
R/W
SM58
1058
Offset calibration Analogue input AI1
SM59
1059
Offset calibration Analogue input AI2
SM60
1060
Offset calibration Analogue input AI3
SM61
1061
Offset calibration Analogue input AI4
SM62
1062
Offset calibration Analogue input AI5
SM63
1063
Offset calibration Analogue input AI6
SM64
1064
Gain calibration Analogue input AI1
SM65
1065
Gain calibration Analogue input AI2
SM66
1066
Gain calibration Analogue input AI3
SM67
1067
Gain calibration Analogue input AI4
SM68
1068
Gain calibration Analogue input AI5
SM69
1069
Gain calibration Analogue input AI6
These words define the calibration of conversion for
AI1..AI6. They are used to correct possible errors of
reading. The formule is as follows:
Value AIx = Value AIx + (Value AIx * Gain calibration
AIx) / 1000 Offset calibration AIx.
At starting all calibration values are set to zero.
R/W