85
7
Yes
Yes
Yes
3
rd
Digit – Select type of degrees
0
Celsius (°C).
1
Fahrenheit (°F).
4
th
Digit – Brightness display 2
0
Higher brightness.
1
Lower brightness
P-52
Block of cycle programming, enable endless step and waiting
function for multi-loop applications
1
st
digit:modify of some or all cycles can be locked to avoid that
specific programmed options are lost due to wrong programming.
2
nd
digit: enable/desable possibility to program endless steps
(step ends only when the operator presses Stop key- see 26.1.2)
3
rd
digit: this option is relevant only for plants with two or more
control loops, it defines max. temperature gap between two or
more zones (ex. kiln with two control zones); if this gap is bigger
than programmed value, cycle stops and controller waits until
uniform values are reached. Beside Waiting function as
described on 31.3, this option assures reliable control of cycle
data.
1
st
Digit –Cycle programming block
0
No block
1..8
Block programming of cycles 1….8
9
Block programming of all cycles
2
nd
Digit – Endless step
0
Endless step enabled
1
Endless step desabled
3
rd
Digit – Double loop: max. gap between process 1-2 for
setpoint block (see 31.4).
0
Gap process 1-2 not considered
1
Gap process 1-2 5 units (ex: 5°C)
2
Gap process 1-2 10 units (ex: 10°C)
3
Gap process 1-2 15 units (ex: 15°C)
4
Gap process 1-2 20 units (ex: 20°C)
5
Gap process 1-2 30 units (ex: 30°C)
6
Gap process 1-2 40 units (ex: 40°C)
7
Gap process 1-2 50 units (ex: 50°C)
8
Gap process 1-2 60 units (ex: 60°C)
9
Gap process 1-2 70 units (ex: 70°C)