27.7 Activate remote setpoint by serial input
20
Set the controller to
mode.
To start the function by serial input, write 1 at modbus address 15:
this operation must be repeated at least every 8 seconds,
otherwise the controller will return to
mode
To quit the function write 0 at the same address.
Setpoint values
must be entered at Modbus address 9 for
process 1 and at address 10 for process 2.
20
To configurate this function, select 0 (remote setpoint) on 4
th
digit of P-01
and “ Remote setpoint by analog input AN2” on 4
th
digit of P-05