User manual -
ATR144- 59
M. rEs.
Manual reset (manual reset by
SET
key or by digital input)
M.rEs.S.
Stored manual reset (keeps the output
status also after a power failure)
A. rEs.t.
Automatic reset with timed activation. The
alarm remains active for the time set on
the parameter
A.1.de.
, even if the conditions
generating it are missing. To be able to act
again, the alarm conditions must disappear.
68
A.1.S.e.
Alarm 1 State Error
Alarm 1 output status in case of error.
If the alarm output is a relay:
open
Contact or valve open.
Default
CLose
Contact or valve closed.
If the alarm output is digital output (SSR):
off
Digital output OFF.
Default
on
Digital output ON.
69
A.1.Ld.
Alarm 1 Led
Defines the status of the led
A1
in correspondence of
the related output
o.c.
ON with open contact or DO switched off.
c.c.
ON with closed contact or DO
switched on. (
Default
)
70
a.1.de.
Alarm 1 Delay
Alarm 1 Delay.
-60:00..60:00 mm:ss (hh:mm if AL.1.F. =
c.aux
).
Default
:
00:00.
Negative value: delay when leaving alarm status
Positive value: delay when triggering alarm status.