56 - ATR144 -
User manual
53
mn.p.1
Minimum Proportional Band 1
Selects the min. proportional band 1 value selectable by
the automatic tune for the P.I.D. regulation of process.
0-10000 [digit
] (degrees.tenths for temp. sensors).
Default: 3.0
54
ma.p.1
Maximum Proportional Band 1
Selects the max. proportional band 1 value selectable
by the automatic tune for the P.I.D. regulation of
process.
0-10000 [digit
] (degrees.tenths for temp. sensors).
Default: 80.0
55
mn.i.1
Minimum Integral Time 1
Selects the min. integral time 1 value selectable by the
automatic tune for the P.I.D. regulation of process.
0.0...1000.0 seconds.
Default
: 30.0 sec.
56
o.c.L.1
Overshoot Control Level 1
The overshoot control function prevents said event
from happening during startup or upon modification of
the setpoint. Setting this value too low could cause the
overshoot to not be fully absorbed, while higher values
might increase the time needed to reach the setpoint.
Disab.
Lev. 1
Lev. 2
Lev. 3
Lev. 4
Lev. 5 (
Def.
)
Lev. 6
Lev. 7
Lev. 8
Lev. 9
Lev. 10
57÷61
Reserved Parameters - Group C
Reserved parameters - Group C.