User manual -
ATR144- 53
12.c
GROUP C -
reG.1
- Autotuning and PID 1
36
tun.1
Tune 1
Selects autotuning type for command 1.
diSab.
Disabled. If proportional band and integral
time parameters are to set to zero, the
regulation is ON/OFF type.. (
Default
)
Auto
Automatic (Automatic P.I.D.
parameters calculation )
Manu.
Manual (launch by keyboards
or by digital input)
OncE
Once (P.I.D. parameters calculation
only at first start)
SYncH.
Synchronized (Autotuning managed by serial)
37
s.d.t.1
Setpoint Deviation Tune 1
Selects deviation from command setpoint 1 as threshold
used by autotuning to calculate P.I.D. parameters.
0-10000 [digit
] (degrees.tenths for temp. sensors).
Default
: 30.0.
38
p.b. 1
Proportional Band 1
Proportional band or process 1 P.I.D. regulation (Process
inertia).
0 ON / OFF if t.i. equal to 0 (
Default
)
1..10000 [digit
] (degrees.tenths for temp. sensors).
39
i.t. 1
Integral Time 1
Integral time for process P.I.D. regulation (process
intertia duration).
0.0...2000.0 sec. (0.0 = integral disabled),
Default
0.0
40
d.t. 1
Derivative Time 1
Derivative time for process P.I.D. regulation (Normally ¼
of integral time).
0.0...1000.0 sec. (0.0 = derivative disabled),
Default
0