User manual - ATR 142
21
7.9
Loading default values
This procedure allows to restore factory settings of the device
Press
Effect
Do
1
FNC
for 3 sec.
Display 1 shows
0000
with the 1st digit
flashing, while display
2 shows
pass
2
or
Change the flashing
digit and move to the
next one using the
SET
key.
Enter password
9999
3
SET
to confirm
Instrument loads
default settings
Turn off and restart
the instrument
7.10
LATCH ON Functions
For use with input
Pot.1
(potentiometer 6KΩ) and
Pot.2
(potentiometer 150KΩ) and with linear input (0…10V,
0...40mV, 0/4…20mA), it is possible to associate start value
of the scale (parameter 6
Lo.L.i.
) to the minimum position
of the sensor and value of the scale end (parameter 7
up.L.i.
)
to the maximum position of the sensor (parameter 8
Latc.
configured as
std.
). It is also possible to fix the point in which
the controller will display 0 (however keeping the scale range
between
Lo.L.i.
and
up.L.i.
) using the “virtual zero” option by
setting
u.0st.
or
u.0in.
in parameter 8
Latc.
If you set
u.0in.
the virtual zero will reset after each activation of the device;
if you set
u.0st.
the virtual zero remains fixed once tuned.
To use the LATCH ON function, configure according to requi-
red operation the parameter
Latc.
2
2
The tuning procedure starts by exiting the configuration after changing
the parameter.