User manual - ATR 142
11
AN1 Analogue Input
-
+
Tc
11
12
Shield/Schermo
For thermocouples K, S, R, J.
• Comply with polarity
• For possible extensions, use
compensated cable and terminals
suitable for the thermocouples
used(compensated)
• When shielded cable is used, it should
be grounded at one side only
10
11
12
PT/NI100
Shield/Schermo
A
B
C
For thermoresistances PT100, NI100
• For the three-wire connection use
wires with the same section
• For the two-wire connection short-
circuit terminals 10 and 12
• When shielded cable is used, it should
be grounded at one side only
10
11
12
RED
WHITE
RED
Shield/Schermo
PTC/NTC
10
11
For thermoresistances NTC, PTC,
PT500, PT1000 e potentiometers
• When shielded cable is used, it should
be grounded at one side only to avoid
ground loop currents
Shield/Schermo
+VDC
9
10
11
12
V/I
+
-
For linear signals V/mA
• Comply with polarity
• When shielded cable is used, it should
be grounded at one side only