Drainage pipe installation
94
Installation
6 Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
Ensure at least 1/100 slope of the drainage pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
6.2.2 Drainage pipe selection
The drainage pipe diameter shall not small than the drain hose of indoor unit
According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu)
Water flowrate (l/h)
12
2.4
18
4
24
6
30
7
36
8
42
10
48
12
60
14
According to the above table to calculate the total water flowrate for the confluence pipe selection.
For horizontal drainage pipe
(The following table is for reference)
PVC pipe
Reference value of
inner diameter of pipe
(mm)
Allowable maximum water flowrate (l/h)
Remark
Slope 1/50
Slope 1/100
PVC25 (1")
20
39
27
For branch pipe
PVC32 (1.25")
25
70
50
PVC40 (1.5")
31
125
88
Could be used for confluence pipe
PVC50 (2")
40
247
175
PVC63 (2.5")
51
473
334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
PVC25 (1")
20
220
For branch pipe
PVC32 (1.25")
25
410
PVC40 (1.5")
31
730
Could be used for confluence pipe
PVC50 (2")
40
1440
PVC63 (2.5")
51
2760
PVC75 (3")
67
5710
PVC90 (4")
77
8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
Summary of Contents for LISAS-B-1403
Page 10: ...Features 12K 18K 8 Indoor Units ...
Page 15: ...Features 24K 36K Indoor Units 13 ...
Page 18: ...Service Space 16 Indoor Units 4 Service Space ...
Page 31: ...Wiring Diagrams Indoor Units 29 ...
Page 46: ...Wiring Diagrams 44 Indoor Units 4 Wiring Diagrams UB012GMFI16MLD UB018GMFI16MLD ...
Page 47: ...Wiring Diagrams Indoor Units 45 UB024GMFI16MLD UB036GMFI16MLD UB048GMFI16MLD ...
Page 52: ......
Page 55: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 56: ...Service Space 54 Indoor Units 3 Service Space ...
Page 57: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams FB012GMFI16MLD ...
Page 61: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M ...
Page 67: ...Wiring Diagrams Outdoor Units 65 4 Wiring Diagrams YN012GMFI16RUD YN018GMFI16RUD ...
Page 68: ...Wiring Diagrams 66 Outdoor Units YN024GMFI16RUD ...
Page 69: ...Wiring Diagrams Outdoor Units 67 YN036GMFI16RUD YN048GMFI16RUD ...
Page 125: ...Troubleshooting Electrical Control System 123 2 4 1 2 Outdoor unit malfunction ...
Page 131: ...Troubleshooting Electrical Control System 129 2 4 4 3 E2 malfunction Only for 12 18K ...
Page 132: ...Troubleshooting 130 Electrical Control System 2 4 4 4 E2 malfunction For 24 48K ...
Page 133: ...Troubleshooting Electrical Control System 131 2 4 4 5 E3 malfunction ...
Page 134: ...Troubleshooting 132 Electrical Control System 2 4 4 6 E4 malfunction ...
Page 136: ...Troubleshooting 134 Electrical Control System 2 4 4 8 E6 malfunction Only for 36K 48K ...
Page 138: ...Troubleshooting 136 Electrical Control System 2 4 4 10 P1 malfunction Only for 36K 48K ...
Page 139: ...Troubleshooting Electrical Control System 137 2 4 4 11 P2 malfunction Only for 36K 48K ...
Page 140: ...Troubleshooting 138 Electrical Control System 2 4 4 12 P3 malfunction ...