Additional refrigerant charge
Installation
99
8 Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process needs to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ6.35 (1/4")
Φ9.52 (3/8")
Formula
V=15g/m×(L-7.5)
V=30g/m×(L-7.5)
V: Additional refrigerant charge volume (g).
L : The length of the liquid pipe (m).
Take the length of your actual pipe, and deduct the 7.5 meter (25') factory pre-charge length from it,
than add 0.5 Oz for every 3.3 additional feet for 1/4" or 1 Oz for every 3.3 feet for 3/8" Liquid line tubing.
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
Summary of Contents for LISAS-B-1403
Page 10: ...Features 12K 18K 8 Indoor Units ...
Page 15: ...Features 24K 36K Indoor Units 13 ...
Page 18: ...Service Space 16 Indoor Units 4 Service Space ...
Page 31: ...Wiring Diagrams Indoor Units 29 ...
Page 46: ...Wiring Diagrams 44 Indoor Units 4 Wiring Diagrams UB012GMFI16MLD UB018GMFI16MLD ...
Page 47: ...Wiring Diagrams Indoor Units 45 UB024GMFI16MLD UB036GMFI16MLD UB048GMFI16MLD ...
Page 52: ......
Page 55: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 56: ...Service Space 54 Indoor Units 3 Service Space ...
Page 57: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams FB012GMFI16MLD ...
Page 61: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M ...
Page 67: ...Wiring Diagrams Outdoor Units 65 4 Wiring Diagrams YN012GMFI16RUD YN018GMFI16RUD ...
Page 68: ...Wiring Diagrams 66 Outdoor Units YN024GMFI16RUD ...
Page 69: ...Wiring Diagrams Outdoor Units 67 YN036GMFI16RUD YN048GMFI16RUD ...
Page 125: ...Troubleshooting Electrical Control System 123 2 4 1 2 Outdoor unit malfunction ...
Page 131: ...Troubleshooting Electrical Control System 129 2 4 4 3 E2 malfunction Only for 12 18K ...
Page 132: ...Troubleshooting 130 Electrical Control System 2 4 4 4 E2 malfunction For 24 48K ...
Page 133: ...Troubleshooting Electrical Control System 131 2 4 4 5 E3 malfunction ...
Page 134: ...Troubleshooting 132 Electrical Control System 2 4 4 6 E4 malfunction ...
Page 136: ...Troubleshooting 134 Electrical Control System 2 4 4 8 E6 malfunction Only for 36K 48K ...
Page 138: ...Troubleshooting 136 Electrical Control System 2 4 4 10 P1 malfunction Only for 36K 48K ...
Page 139: ...Troubleshooting Electrical Control System 137 2 4 4 11 P2 malfunction Only for 36K 48K ...
Page 140: ...Troubleshooting 138 Electrical Control System 2 4 4 12 P3 malfunction ...