Electrical Control Function
Electrical Control System
107
For Ceiling-floor (12-24K), Cassette (12-24K), Concealed Ducted (12-24K)
4
3
High
Low
1
Medium
1.5
For other units:
5.0
4.0
High
Low
2.0
Medium
3.0
1.3.2.4 Evaporator low temperature T2 protection.
For 12K-24K units,
---T2<0
℃
, the compressor will stop and restart when T2
≥
5
℃
.
---0
℃≦
T2<4
℃
, the compressor frequency will be limited and decreased to the lower level every 1 minute till
off.
---4
℃
≤T2≤7
℃
, the compressor will keep the current frequency.
---T2>7
℃
, the compressor frequency will not be limited.
For other units:
When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume till
T2
≥
7
℃
.
1.3.2.5 Condenser high temperature T3 protection
For 12K-18K Outdoor units
:
---55
℃
<T3<60
℃
, the compressor frequency will decrease to the lower level every 3 minutes till F1 and then
runs at F1.If T3<54
℃
, the compressor will keep running at the current frequency.
---T3<52
℃
, the compressor will not limit the frequency and resume to the former frequency.
---T3>60
℃
for 5 seconds, the compressor will stop until T3<52
℃
.
For other units:
When T3>65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the compressor
will restart.
Summary of Contents for LISAS-B-1403
Page 10: ...Features 12K 18K 8 Indoor Units ...
Page 15: ...Features 24K 36K Indoor Units 13 ...
Page 18: ...Service Space 16 Indoor Units 4 Service Space ...
Page 31: ...Wiring Diagrams Indoor Units 29 ...
Page 46: ...Wiring Diagrams 44 Indoor Units 4 Wiring Diagrams UB012GMFI16MLD UB018GMFI16MLD ...
Page 47: ...Wiring Diagrams Indoor Units 45 UB024GMFI16MLD UB036GMFI16MLD UB048GMFI16MLD ...
Page 52: ......
Page 55: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 56: ...Service Space 54 Indoor Units 3 Service Space ...
Page 57: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams FB012GMFI16MLD ...
Page 61: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M ...
Page 67: ...Wiring Diagrams Outdoor Units 65 4 Wiring Diagrams YN012GMFI16RUD YN018GMFI16RUD ...
Page 68: ...Wiring Diagrams 66 Outdoor Units YN024GMFI16RUD ...
Page 69: ...Wiring Diagrams Outdoor Units 67 YN036GMFI16RUD YN048GMFI16RUD ...
Page 125: ...Troubleshooting Electrical Control System 123 2 4 1 2 Outdoor unit malfunction ...
Page 131: ...Troubleshooting Electrical Control System 129 2 4 4 3 E2 malfunction Only for 12 18K ...
Page 132: ...Troubleshooting 130 Electrical Control System 2 4 4 4 E2 malfunction For 24 48K ...
Page 133: ...Troubleshooting Electrical Control System 131 2 4 4 5 E3 malfunction ...
Page 134: ...Troubleshooting 132 Electrical Control System 2 4 4 6 E4 malfunction ...
Page 136: ...Troubleshooting 134 Electrical Control System 2 4 4 8 E6 malfunction Only for 36K 48K ...
Page 138: ...Troubleshooting 136 Electrical Control System 2 4 4 10 P1 malfunction Only for 36K 48K ...
Page 139: ...Troubleshooting Electrical Control System 137 2 4 4 11 P2 malfunction Only for 36K 48K ...
Page 140: ...Troubleshooting 138 Electrical Control System 2 4 4 12 P3 malfunction ...