SDD ES PROFINET
Operating Manual SDD ES PROFINET
1003826-EN-01
25
Message
number
Message text
Meaning/action
0x304
Power ↓, please ↑
Supply voltage is at the lower limit
of the permitted range (see Tech-
nical details for safety device)
}
Ensure the supply voltage cor-
responds to the Technical de-
tails for the connected safety
device.
0x305
Actuator
Wrong actuator signalled on
unique or fully coded versions of a
safety device
}
Use the actuator stated in the
operating manual for the
safety device.
0x306
Actuator ♥
New actuator has been taught in
}
Switch supply voltage off and
then on again.
0x320
Lock
Guard locking could not be activ-
ated or deactivated.
}
Check the wiring of the control
and the actuator.
0x321
Lock
Guard locking is in a not defined
position.
}
Use the escape release to
move the guard locking into
the open state.
Switch the voltage off and then
on again
0x900
0x901
**Start UP**
Fieldbus module and communica-
tion with the safety devices have
been restarted
0x903
Please ↔ Device
Internal error
}
Change the safety device.
0x904
Please Reset
Internal error
}
Check the wiring and switch
the voltage off and then on
again.
0x905
OSSD 1&2
Fault on the safety device output
}
Check the wiring and switch
the voltage off and then on
again.