Firmware update
The firmware and the web server of SDD ES PROFINET can be updated.
1. Set the IP address of the configuration PC to the address range of the SDD ES
PROFINET (e.g. 192.168.0.1).
To access SDD ES PROFINET, the IP address of the PC has to be in the same subnet
as the IP address of SDD ES PROFINET
Change the IP address in the network settings of your configuration PC or change the
IP address of the SDD ES PROFINET (see Set IP address).
2. Establish an FTP connection to the Gateway, using the user name "Admin" and pass-
word "0000".
3. Copy the file "SDD_xxx.kfu" and the directory "web" with FTP to the SDD ES
PROFINET and save the files in the topmost directory.
4. Perform a restart of SDD ES PROFINET. The changed configuration is therefore adop-
ted.
Messages for safety device diagnostics
Message
number
Message text
Meaning/action
0x300
Safety Gate!
The actuator has changed state
quickly.
}
Check and correct the mis-
alignment of switch and actu-
ator and correct if necessary.
0x301
Input
Safety device in partially operated
status
}
Check the wiring.
0x302
Input , Restart
Safety device in partial operation
lock status
}
Check the wiring and switch
the voltage off and then on
again.
0x303
Power ↑, please ↓
Supply voltage is at the upper limit
of the permitted range (see Tech-
nical details for safety device)
}
Ensure the supply voltage cor-
responds to the Technical de-
tails for the connected safety
device.