PSEN ma1.4-51 M12/8-0.15m
Operating Manual PSEN ma1.4-51 M12/8-0.15m
22185-EN-05
9
Actuator PSEN ma1.4-10
Assured operating distance S
ao
in mm
Vertical offset
Lateral offset
0 mm
2 mm
4 mm
6 mm
8 mm
0 mm
10.0
10.0
9.0
7.0
5.0
2 mm
10.0
10.0
8.0
6.0
3.0
4 mm
9.0
8.0
7.0
5.0
-
6 mm
7.0
6.0
5.0
-
-
The stated values are valid at a temperature of 20 °C.
Wiring
}
Information given in the
Technical details [
17]
must be followed.
}
Calculation of the max. cable length l
max
:
R
lmax
- R
i
R
l
/ km
I
max
=
R
lmax
= Max. overall cable resistance (see evaluation device's technical details)
Ri = Internal resistance sensor (see
Technical details [
17]
)
R
l
/ km = Cable resistance/km of the cable (see technical details cable)
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
In the following cases, check the function that detects shorts across contacts prior to
commissioning:
– On evaluation devices with DC supply voltage: Overall cable resistance ≥ 15 Ohms
per channel
– On evaluation devices with AC supply voltage: Overall cable resistance ≥ 25 Ohms
per channel
– For details of how to perform the test for shorts across the contacts, please refer to
the operating manual for the relevant evaluation device.
Pin assignment
NOTICE
The colour marking for the connection lead only applies for the cable that
Pilz supplies as an accessory
The safety switch is shown in an unoperated condition.