Connecting the auxiliary contact to an eval-
uation device
Connecting the auxiliary contact to a PLC
Installation
}
The unit can be installed in any position. However, safety switches and actuators must
be positioned opposite each other in parallel.
}
If possible, do not install the safety switch and actuator on to ferromagnetic material.
Changes to the operating distances are to be expected.
}
Safety switches and actuators should only be secured using M4 screws with a flat head
(e.g. M4 cheese-head or pan head screws). Use screws made of non-magnetic mater-
ial (e.g. brass).
CAUTION!
Potential loss of safety function due to changed device properties
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material.
– Please check the operating distances and the assured release dis-
tance.
CAUTION!
Possible loss of the safety function by changing the release distance S
ar
with non-flush installation
Installing the safety switch non-flush within electrically or magnetically con-
ductive material, the value for the assured release distance
S
ar
can change.
– Check the assured release distance
S
ar.
}
Safety switches and actuators must be positioned so that they are secured against a
change of position.