PSEN cs2.13p ATEX
Operating Manual PSEN cs2.13p ATEX
21133-EN-17
| 13
}
The inputs and outputs of the safety switch must have a protective separation to voltages
over 60 VDC.
INFORMATION
Only use safety relays with a 24 VDC supply voltage. Safety relays with a
wide-range power supply or in AC device versions have internal potential
isolation and are not suitable as evaluation devices.
}
The supply voltage to the safety switch must be protected with a 2 A to 4 A quick-acting
fuse.
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
Refer to the notes on wiring in EN 60079-14.
}
When connecting in series, consider the requirements of manipulation protection and the
protection against bypassing or from overriding the safety switch (EN ISO 14119).
}
Ensure that the connector of the safety switch in the EX area is not removed or inserted.
}
Any metallic parts (also accessories) must be connected to the equipotential bonding in
case of a risk of charging.
Terminal assignment connectors
8-pin M12 connector
PIN
Connection
designation
Function
Wire colour
1
S21
Input, channel 2
white
2
A1
+24 VUB
brown
3
12
Output, channel1
green
4
22
Output, channel2
yellow
5
Y32
Signal output/diagnostic output
grey
6
S11
Input, channel 1
pink
7
A2
0 V UB
blue
8
Y1
Diagnostics input
red
The wire colour also applies for the cable available from Pilz as an accessory.