72
8.10 List of real-time measured data registers
Register
address
Definition
Data type
Description
40101
Phase A voltage
40102
Phase B voltage
40103
Phase C voltage
Calculation factor: 0.01, unit: V
40104
Phase voltage unbalance
rate
Calculation factor: 0.001
40105
Average phase voltage
40106
Line AB voltage
40107
Line BC voltage
40108
Line CA voltage
Calculation factor: 0.01, unit: V
40109
Line voltage unbalance
rate
Calculation factor: 0.001
40110
Average line voltage
40111
Neutral voltage
UINT16
Calculation factor: 0.01, unit: V
40112
Phase A current
40113
Phase B current
40114
Phase C current
Calculation factor: 0.001, unit: A
40115
Current unbalance rate
Calculation factor: 0.001
40116
Average phase current
40117
Neutral current
UINT16
Calculation factor: 0.001, unit: A
40118
Phase A active power
INT16
Calculation factor: 0.1, unit: W