56
5.4 Analog output
PMAC735 can provide one optional 4-20 mA analog output, supporting the access of the DCS
system. The user can, through the communication interface, set the parameter value
corresponding to the analog output. The maximum load resistance of the interface should not
exceed 500 Ohms.
On some sites, due to different transmission cables or loading conditions, the analog output at the
high end appears to be non-linear. PMAC735 provides a settable magnification factor. By
modifying the magnification factor, the user can adjust the proportion factor of the output curve.
The figure below shows the analog output characteristic curve, and the magnification factor is
λ
: