Manual MSD2
+
MA 2126
–A005 EN
22
6.3 Cable
Overview:
max. cable
length [m]
min. cross
section
[mm
2
]
shielded,
grounded
on all
sides
Motor cable
25
0.1/1 A
X
50
0.2/1 A
X
Signal interface
30
0.14
X
ServiceBus cable
2
–
Motor cable
We recommend wiring the stepper motor with a 5-lead cable with shielding mesh. For
optimum electromagnetic compatibility (EMC), the cable should not be interrupted by
additional connectors or screw terminals.
The PE conductor (green/yellow) of the motor cable is connected to the PE contact of the
5-pole motor plug. On the motor side, the PE conductor must be connected to the earthing
screw of the motor.
The motor cable length depends on the cable resistance: R
cable
< 0.2 x R
Phase
We recommend the following lead cross section of the motor cable
:
stepper motor current
cable cross section
5 A
0.75 mm
2
10 A
1.00 mm
2
15 A
1.50 mm
2