main unit and the modules. Note how the wiring is reversed between the modules and the
main unit, but between modules the wiring is straight through.
Figure 3: Communications Bus Wiring
The modules may be located up to 2000 feet away from the main unit. Do not run AC power
lines in the same cable or conduit as the communications wiring, as this can cause data errors.
Bus Termination
Both the SCADA 3000 main unit and the final module in the chain must be terminated. A
termination jumper is located on each device. The modules (if any) branching off the main
connection are not terminated. While the main connection between the SCADA 3000 and the
most distant module can be 2000 ft., the individual modules in-between are wired on branches
called Stub lines. Stub lines can be no more than 50 ft. from the main line.
(See Figure 4)
Figure 4: Communication Cable Wiring and Bus Termination
7-3
Chapter 7: I/O Expansion Modules
Summary of Contents for Sensaphone SCADA 3000
Page 1: ...Sensaphone SCADA 3000 User s Manual Version 2 34...
Page 6: ...vi SCADA 3000 User s Manual...
Page 10: ...x SCADA 3000 User s Manual...
Page 30: ...1 6 SCADA 3000 User s Manual...
Page 48: ...4 6 SCADA 3000 User s Manual...
Page 70: ...9 8 SCADA 3000 User s Manual...
Page 122: ...12 8 SCADA 3000 User s Manual...
Page 190: ...15 30 SCADA 3000 User s Manual...
Page 211: ...lead 1 lag 0 else lead 0 lag 1 16 21 Chapter 16 Programming in C...
Page 212: ...16 22 SCADA 3000 User s Manual...
Page 236: ...21 8 SCADA 3000 User s Manual...
Page 248: ...22 12 SCADA 3000 User s Manual...
Page 258: ...23 10 SCADA 3000 User s Manual...
Page 274: ...25 8 SCADA 3000 User s Manual...
Page 288: ...27 8 SCADA 3000 User s Manual...
Page 294: ...28 6 SCADA 3000 User s Manual...
Page 296: ...A 2 SCADA 3000 User s Manual...
Page 302: ...D 2 SCADA 3000 User s Manual...
Page 318: ...I 2 SCADA 3000 User s Manual...
Page 320: ...J 2 SCADA 3000 User s Manual...
Page 322: ...K 2 SCADA 3000 User s Manual...
Page 335: ...Test Log...
Page 336: ......