2. Press STATUS.
STATUS
The Model 800 audibly recites the current status of every zone. In
a Status Report, each zone is first identified by its zone number,
followed by a report that specifies parameters currently affecting
that zone.
If a zone is disabled, the word “Alarm Disabled”
immediately follows the number recited for that zone.
For example, zone 3 is configured as a normally open, dry contact
zone. During the Status Report:
•
If disabled
, the Model 800 recites:
“Zone 3, the Alarm is Disabled”
for zone 3.
•
If enabled
, the Model 800 recites:
“Zone 3—OK,”
for zone 3.
In another example, zone 2 is configured as a temperature zone.
The current temperature is 76 degrees. During a Status Report:
•
If disabled
, the Model 800 recites:
“Zone 2, the alarm is disabled, it is now 76 degrees
fahrenheit—OK”
•
If
enabled
, the Model 800 recites:
“Zone 2—76 degrees fahrenheit—OK.”
5.3 Zone Recognition Time
The Zone Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-out
is activated. This time period is programmable, from 0 minutes, 0
seconds (for immediate response) up to a period of 540 minutes,
0 seconds. If an alert condition begins and then clears within the
established Recognition Time, no dial-out will occur. When an
alert condition continues beyond the programmed Recognition
Time, the Model 800 initiates dial-out. The default setting for
Zone Recognition Time is 0 minutes, 3 seconds.
5.3.1 Programming Zone Recognition Time
1. Press SET.
SET
Sensaphone
®
Model 800 User’s Manual
71
Summary of Contents for Sensaphone 800
Page 2: ......
Page 3: ...SENSAPHONE Model 800 User s Manual Version 1 1 PHONETICS INC ...
Page 14: ...Sensaphone Model 800 User s Manual xii ...
Page 20: ...xviii ...
Page 42: ...Sensaphone Model 800 User s Manual 39 ...
Page 70: ...Sensaphone Model 800 User s Manual 67 ...
Page 130: ...127 ...
Page 132: ...129 ...
Page 136: ...133 ...