PSR-CT
PHOENIX CONTACT
108366_en_01
4.4.1
Checking the planned design
Check the planned design using Table 4-3 “Example table for cable lengths”. Proceed as
described in the example.
See “Example: determining the cable length” on page 37.
The information on the cable lengths applies under the following conditions:
–
The requirements on the connecting cables according to Table 4-1 are adhered to.
Table 4-3
Example table for cable lengths
n
Maximum number of
switches
i
out
[mA]
Possible output current per
channel FO1A/FO1B
l1 [m]
Maximum cable length from
the last switch to the control-
ler
0.34 mm² cable
5
10
100
25
100
50
80
100
50
6
10
100
25
90
50
70
100
50
10
10
70
25
60
50
50
100
35
Note that connecting a reset button will influence the cable length design.