Electrical connection
108366_en_01
PHOENIX CONTACT
Example: determining the cable length
–
Six switches in series are to be used.
–
The cable length from the safety relay in the control cabinet to the last switch
(PSR-CT 6) is 40 m.
–
The cable length between each individual switch is 20 m.
–
The safety relay consumes 75 mA at each of the two safe inputs.
Figure 4-2
Switch chain with six PSR-CT safety switches
Determine the relevant values using the example table:
1.
In
column n
, select the corresponding section.
–
In this example, six switches.
2.
In the selected section, search
column i
out
for a current
≥
75 mA.
–
In this example: 100 mA.
3.
In the same line, read the maximum cable length from the last switch (PSR-CT 6) to the
controller from
column l
1
.
–
In this example: 50 m.
Result:
–
With a length of 40 m, the desired cable length l
1
is lower than the permissible value in
–
The total length of the switch chain l
target
is 140 m and therefore lower than the maxi-
mum value according to Table 4-2 (l
max
= 200 m for
20 switches).
The planned application in this format is operational.
PSR-CT 6
PSR-CT 5
PSR-CT 4
PSR-CT 3
l
1
= 40 m
l
2
= 5 x 20 m
l
nom
= 140 m
l
n
= 20 m
i
out
= min. 75 mA
PSR-CT 2
PSR-CT 1
Phoenix Co
ntact Saf
ety R
ela
y