Technical data and ordering data
108366_en_01
PHOENIX CONTACT
Utilization category according to IEC 60947-5-2
150 mA (24 V (DC13))
Note on protective circuit
NOTE:
Protect the outputs under inductive loads with a free-
wheeling diode.
Residual current
≤
0.25 mA
Signal outputs
Designation
DGN
Output description
Sourcing
Number of outputs
1
Short-circuit proof
Yes
Output voltage
U
B
- 1.5 V, minimum (HIGH)
U
B
, maximum
(HIGH)
0 V DC, minimum (LOW)
1 V DC, maximum (LOW)
Current I
DGN
1 mA, minimum
50 mA, maximum
Times
Switch-on delay
5 s, typical (after switching on U
B
)
Risk time according to EN 60947-5-3
125 ms, maximum (stand-alone device)
Delay time
10 ms, typical (risk time delay per device)
Switch-on time
400 ms, maximum (of the safety outputs)
Discrepancy time
10 ms, maximum (between the safety outputs)
Test pulses
300
μ
s, typical (test pulse duration)
100 ms, approximately (test pulse interval)
Safety outputs