Configuration and startup
103503_en_03
PHOENIX CONTACT
5-5
Once the connecting cable has been connected, the correspondingly configured PC
detects the safety module automatically and indicates the safety module status at the
bottom right in the status bar (see Figure 4-1 on page 4-3).
Figure 5-4
USB connection between PC and safety module
3.
The project can only be downloaded to the PSR-TRISAFE-S safety module if you have
logged on in SAFECONF with the correct
controller password
. In the "Safe
Controller" menu, select "Log On", enter the controller password in the dialog box and
click "OK".
4.
Provided that the current project has been checked and has
no errors
(see page 4-18
or the SAFECONF online help), the project loaded in SAFECONF can be downloaded
to the safety module by clicking on the following icon in the toolbar:
Is there already a project on the safety module?
If the status bar has a yellow entry on the right "Controller: No project", the project is
transmitted to the safety module without any further prompts.
If another project or another version of the same project is already available on the
safety module and is being executed, a corresponding dialog box appears, indicating
this fact. Click "Yes" in this message dialog box to overwrite the current controller
configuration on the safety module.
During data transmission
–
A progress indicator is displayed in the SAFECONF status bar.
–
The "CONF" status indicator flashes quickly on the PSR-TRISAFE-S safety
module (approximately 6 Hz).
5.
Once data transmission has been completed successfully, the "CONF" status indicator
flashes slowly (approximately 1.5 Hz) and a corresponding message dialog box
appears in the configuration software.
If the data transmission is interrupted during the download, please refer to "Problems and
Status indicator for
PSR-TRISAFE-S
"CONF" LED flashes during
data transmission
Summary of Contents for 2986229
Page 2: ......
Page 32: ...PSR TRISAFE S 2 16 PHOENIX CONTACT 103503_en_03...
Page 50: ...PSR TRISAFE S 3 18 PHOENIX CONTACT 103503_en_03...
Page 74: ...PSR TRISAFE S 4 24 PHOENIX CONTACT 103503_en_03...
Page 88: ...PSR TRISAFE S 5 14 PHOENIX CONTACT 103503_en_03...
Page 90: ...PSR TRISAFE S 6 2 PHOENIX CONTACT 103503_en_03...
Page 96: ...PSR TRISAFE S 7 6 PHOENIX CONTACT 103503_en_03...