Function test
Validation
Once the project has been loaded onto the PSR-TRISAFE-S safety module and executed
from this point (following manual confirmation), you must perform a function test to ensure
that the safety module is working correctly and, therefore, that the safety logic and all the
cabling are working correctly as well.
Online mode in
SAFECONF
To support you in this, you can switch the SAFECONF configuration software to online
mode so that online values can be read cyclically from the safety module and displayed in
the connection editor and the hardware editor.
Safety
demand/monitoring
signals
Once a safety demand has been triggered by activating the safe control devices, e.g., by
pressing the emergency stop control device or opening the safety door, the behavior of the
safety logic can be analyzed precisely in the configuration software, as in online mode the
connection editor displays the value of every signal "live".
To execute a function test, proceed as follows:
Connected/logged on
1.
Connect the PSR-TRISAFE-S safety module, which is switched on, to the configuration
computer via the USB interface, start the SAFECONF configuration software, and log
on for the safety module.
The status bar in SAFECONF displays the following entry on the right-hand side.
2.
Switch SAFECONF to online mode by clicking on the "Online Values" icon in the
toolbar:
"Signal lines" and functional block connections are now displayed in the connection
editor in different colors, according to their state (TRUE/FALSE), and together with the
current values. The hardware editor also supports the function test through "lit" LEDs.
WARNING: Risk of injury or damage to equipment due to unintentional system
states or incorrect responses.
Make sure that the act of triggering the safety demand will not pose a risk for people or
materials.
The safety module is in the startup phase, i.e., unintentional system states or incorrect
responses cannot be ruled out.
Do not enter any hazardous areas and ensure that no other persons can access the
danger zone either.
The system can only display online values if the project in the safety module and the
project in the configuration system are identical. If you have made a change to a project
after startup (even something as small as moving an object is classed as a change), you
must check the project and send it to the safety module again before you can display
online values.
Summary of Contents for 2986229
Page 2: ......
Page 32: ...PSR TRISAFE S 2 16 PHOENIX CONTACT 103503_en_03...
Page 50: ...PSR TRISAFE S 3 18 PHOENIX CONTACT 103503_en_03...
Page 74: ...PSR TRISAFE S 4 24 PHOENIX CONTACT 103503_en_03...
Page 88: ...PSR TRISAFE S 5 14 PHOENIX CONTACT 103503_en_03...
Page 90: ...PSR TRISAFE S 6 2 PHOENIX CONTACT 103503_en_03...
Page 96: ...PSR TRISAFE S 7 6 PHOENIX CONTACT 103503_en_03...