Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 15
If no philippi ACE series charger is connected or the charger is not supplied with mains voltage, no
settings can be made.
4.5 Alarm
A tank alarm is always indicated by the associated tank symbol flashing. A battery alarm is always
displayed in the battery symbol. In addition, the alarm can be issued/configured as follows:
-
optical
Display illumination flashes
-
Audible
internal buzzer
-
Relay contact
potential-free relay (max. 1A)
The optical and acoustic alarm can always be acknowledged in advance by touching the screen or
can switch off automatically after a definable time.
Alarm options:
Tank alarms:
An alarm threshold can be set individually
for
each of the 4 tanks. The following settings are
possible
:
0 %Alarm off1
..50 %.
Empty alarm: if the fill level falls below the set value,
alarm is triggered. The alarm triggering is delayed by 15s.
51... 99 %
Full alarm: if the fill level rises above the set value,
the alarm is triggered. The alarm is delayed by 15s.
The alarm is automatically cancelled as soon as the value has changed by 5%.
By briefly pressing the respective line, the acoustic alarm can be switched on or off. By pressing
and holding (> 2s), the respective threshold value can be edited.