Step 4: Make the Grounding Shield
Leave 65mm Shield as the grounding shield and turn it to the outside of the coat. Then, weld a wire
on the shield as the drainage line.
Step 5: Fix the Grounding Shield
Use a 60mm heat-shrink tube to fix the grounding shield and leave 40mm shield outside.
Step 6: Make the Phase Wires
Choose 2 wires of the cable as DC+ and DC-. Crimping pre-insulated Terminals on the wires will
enhance the connection stability and simplicity between the cable and drive. AxN Size5 series
drives are recommended to use the RNY series Ring Terminals manufactured by KST. Refer to the
following table to select the appropriate terminal:
AxN Size5
Ring
Terminals
d2(mm) W(mm) F(mm)
E(mm)
D(mm) d1(mm)
AxN 90.150.4
RNYB22-8
8.4
16.5
13.5
24
13
7.7
AxN 110.200.4
RNYB22-8
8.4
16.5
13.5
24
13
7.7
Strip the wires for L mm (1 ≤ L ≤ E), the recommend strip length is E/2 mm, refer to the following
table to select an appropriate length:
AxN Size5
Strip Length (mm)
Recommended Strip Length (mm)
AxN 90.150.4
1 ~ 24
12
AxN 110.200.4
1 ~ 24
12