8
2
Main Circuit Wiring
2.1
AC Power Supply Input
2.1.1
AC Power Supply Requirement
Mains Supply
AxN Series
Voltage
150
~
500Vac
Type
Three-phase AC power
Frequency
50/60Hz
Fluctuation of Frequency
±10% (45
~
66Hz)
Asymmetry
±3%
2.1.2
AC Power Supply Cable Fabrication
AC power supply cable is the cable which connect the AxN Size5 Drive with the filter. The
connection between AC power supply and the filter is not mentioned in this manual, and should
be connected properly based on the real application.
Step 1: Cable Selection
AxN Size5 drive must use a 4 wire cable with shield as its AC power supply cable. Refer to the
table below to select the appropriate cable:
AxN Size5
Current (A rms)
Recommended
Gauge (mm
2
)
Recommended
Gauge (AWG)
AxN 90.150.4
90
21.15
4
AxN 110.200.4
110
26.67
3
Step 2: Cable Length Measurement
The AC power supply cable is used to connect the output of the filter with the Power Input Port
(P1) of AxN Size5 Drive. To minimize the interference, the filter must be installed in close proximity
to AxN Size5 Drive as much as possible. But, the distance between two devices should also comply
with the Installation Space Regulation of AxN Size5 Drive (Refer to
1.5 Installation Spacing
).
NOTE:
The length of AC power supply cable should
NOT
exceed
0.5m
.
Step 3: Strip the Cable Coat
Strip the outside coat of the AC power supply cable for 160mm and reveal the inside shield.
Summary of Contents for AxN series
Page 2: ......
Page 7: ...5 1 3 Overall Dimensions...
Page 32: ...30...
Page 37: ...35 When the drive is ready N O connects Com and N C disconnects Com illustrated as below...