4
1.2
Installation Environment
To help prolong the optimum performance life of the drive, install the drive in the proper
environment. The table below provides description of the appropriate environment for the drive.
Environment
Condition
Installation Area
Indoor
Ambient
Temperature
0
℃
to 40
℃
, up to 50
℃
with power reduction (2%/
℃
)
Drive reliability improves in environments without wide temperature
fluctuations.
When using an enclosure panel, install a cooling fan or air conditioner in the
area to ensure that the air temperature inside the enclosure does not exceed
the specified levels.
Do not allow ice to develop on the drive.
Humidity
5 to 90% without condensation
Surrounding Area
Install the drive in an area free from:
1.
oil mist and dust
2.
metal shavings, oil, water or other foreign materials
3.
radioactive materials
4.
combustible materials (e.g., wood)
5.
harmful gases and liquids
6.
excessive vibration
7.
chlorides
Altitude
Up to 1000m above MSL, over 1000 m above MSL with power reduction ( 3%
per 100m)
Vibration
Amplitude up to 0.3mm at 2 to 9 Hz
Acceleration up to 1m/s
2
at 9 to 200 Hz
Orientation
Install the drive vertically to maintain maximum cooling effects.
Summary of Contents for AxN series
Page 2: ......
Page 7: ...5 1 3 Overall Dimensions...
Page 32: ...30...
Page 37: ...35 When the drive is ready N O connects Com and N C disconnects Com illustrated as below...