Installing the VisuNet GXP
1.
Connect the AG1 housing to an external equipotential bonding conductor.
2.
Close the AG1 housing, but do not yet insert the screws to fasten the housing closed.
3.
Insert the 19-inch VisuNet GXP into the opening of the AG1 housing. Be sure to wear safety
gloves to protect your hands.
4.
Ensure that no foreign bodies are attached either to the front plate of the VisuNet GXP or to the
connection surface of the AG1 housing. If necessary, clean the surfaces with methylated spirit
or cold cleaner before installing the VisuNet GXP.
5.
While securing the VisuNet GXP housing to prevent it from falling, swing the AG1 front housing
sideways along with the GXP.
6.
Tighten the self-locking nuts onto the threaded pins on the front plate using the magnetic
wrench.
7.
Connect the equipotential bonding conductor between the AG1 housing and the VisuNet GXP.
Note
Check the surrounding seal of the front plate for damage before installing the
VisuNet GXP.