Mechanical Installation

3.3.3

Preparing the StandardLine Pedestal

A variety of pedestals are available for floor mounting. For a complete list of available mounting 
options, see the mounting options datasheet. Pedestals are shipped with an attached protec-
tive earth (PE) wire and screws for mounting the VisuNet GXP AG1 housing to the pedestal: 6 x 
M8 countersunk screws and 2 x M6 countersunk screws.

StandardLine Pedestal

1

Pre-installed PE wire

2

Top cable opening

3

Cable glands

1

2

3

Summary of Contents for VisuNet GXP Series

Page 1: ...VisuNet GXP RM GXP1100 19S RM GXP1200 19S PC GXP1100 19S PC GXP1200 19S Manual...

Page 2: ...ion as well as the supplementary clause Expanded reservation of proprietor ship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs c...

Page 3: ...g the GXP Panel Housing 17 3 3 3 Preparing the StandardLine Pedestal 20 3 3 4 Attaching the Pedestal to the Housing 24 3 3 5 Opening the Housing 27 3 3 6 Grounding the Housing to the Pedestal 29 3 3 7...

Page 4: ...ion certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Additional documents 1 2 Target Group Personnel Responsibility for planning assembly commissioning...

Page 5: ...in descending order as fol lows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indica...

Page 6: ...DPU1200 are display panels with optional 10 finger multi touch sensors The displays and touch sensors are optically bonded with the hard ened front glass The thin client units TCU1100 and TCU1200 are...

Page 7: ...nel Components 1 Bezel for housing and panel mounting 2 Computing unit TCU or PCU processor SSD and memory Ex circuits interface modules 3 Power supply unit DC or AC option backpacked panel mount or s...

Page 8: ...yboard mouse ordered separately VisuNet GXP Pedestal Mounted with Keyboard Mouse Note For a description of the product model nomenclature see the VisuNet GXP PC or VisuNet GXP RM product datasheets at...

Page 9: ...MB DDR3L Mass storage 32 GByte industrial grade MLC SSD Software Operating system VisuNet RM Shell 5 x based on Microsoft Windows 10 IoT LTSB Hardware Processor Intel Atom Bay Trail E3845 1 91 GHz RA...

Page 10: ...1 x RS 232 interface with Power Supply for miscellaneous devices and periph erals Ex i 1 x RS 232 Ex e 1 x RS 485 Ex e 1 x Ethernet 100 1000Base TX Ex e Bluetooth v4 0 communication distance up to 30...

Page 11: ...453 mm x 137 mm panel with AG1 housing 582 mm x 490 mm x 224 mm Note For more technical information refer to the manuals and instruction manuals of the individual components Display Units DPU1100 J1 a...

Page 12: ...2 3 Dimensions Dimensions with AG1 Housing and Pedestal Figure 2 3 Dimensions with StandardLine Pedestal5 1458 Fix and EXTA2 keyboard mouse sample configuration 582 490 1702 228 475 1100 Note Keyboard...

Page 13: ...GXP Product Description 2020 04 13 Panel Dimensions with Bezel Panel Cut Out Dimensions Cut out dimensions 480 x 400 mm For more information see chapter 3 5 524 137 453 499 480 167 419 400 270 6 5 0...

Page 14: ...2 4 Wall mount dimensions with additional wall brackets 198768 2 4 Disposal Follow all local and any other requirements for disposing of electronic equipment When dis posing of any system component m...

Page 15: ...device available The safety of any system incorporating the power supply unit is the responsibility of the assembler of the system 3 2 Installation Tools 4 mm and 5 mm torque Allen keys Open ended wr...

Page 16: ...s the installer s responsibility to select a suitable location with sufficient strength to hold the equipment It is the installer s responsibility to select the proper screws based on the installa tio...

Page 17: ...mponents 1 x pre assembled VisuNet RM GXP or PC GXP panel option panel mounted into AG1 housing 2 x protective tubes Screws for housing EXTA2 keyboard and PEDESTAL5 xxxx ordered separately StandardLin...

Page 18: ...Lifting the GXP housing on your own may cause injury Do not attempt to lift the device on your own Use a crane or have another person help you Warning Danger resulting from scratched display unit scre...

Page 19: ...VisuNet GXP Mechanical Installation 2020 04 19 4 Remove and discard the screws from the bottom of the housing...

Page 20: ...mplete list of available mounting options see the mounting options datasheet Pedestals are shipped with an attached protec tive earth PE wire and screws for mounting the VisuNet GXP AG1 housing to the...

Page 21: ...ate cable entry 3 Put the gland nut and ferrule of the cable gland on the cable and slide them a few meters down the length of the cable away from the pedestal Keep the nut and ferrule on the cable in...

Page 22: ...2020 04 22 VisuNet GXP Mechanical Installation 4 Attach the cable to the pull wire...

Page 23: ...the cable through the cable entry and out the top of the pedestal 6 Pull the cable through the pedestal so that 50 cm of cable is hanging out of the top of the pedestal 7 Repeat the preceding steps fo...

Page 24: ...bottom of the housing 3 Align the mounting holes on the top of the pedestal with the mounting holes on the back of the housing Warning Risk of injury Lifting the GXP housing on your own may cause inj...

Page 25: ...VisuNet GXP Mechanical Installation 2020 04 25 4 Tighten the 6 x M8 screws in a criss cross pattern to 20 Nm 5 Tighten the 2 x M6 screws to 12 Nm...

Page 26: ...e plastic film from the screen This should not be present in a hazardous location Warning Proper floor mounting It is the installer s responsibility to select a suitable location with sufficient stren...

Page 27: ...g the GXP 1 Loosen the 4 screws on the back of the housing 2 Gently pull the front side of the housing toward you Warning Risk of Damage and Injury Opening the GXP housing before the pedestal is mount...

Page 28: ...2020 04 28 VisuNet GXP Mechanical Installation 3 Pull the right side of the housing front away from the back part of the housing...

Page 29: ...edestal comes with a pre installed PE wire that you must route from the pedestal into the housing see see chapter 3 3 3 Connecting the PE Wires 1 Remove the nuts and washers from the PE stud on the in...

Page 30: ...l Installation 3 Replace the nuts and washers Fasten the nuts and washers with a torque of 7 5 Nm Figure 3 2 Grounding Concept 1 Housing 2 PE stud hexagon socket 3 Contact washer 4 Nut 5 Cable lug 6 F...

Page 31: ...31 3 3 7 Mounting the Keyboard 1 Remove the plug and screws from the bottom of the housing 2 To remove the plug open the housing see see chapter 3 3 5 Hold the the inside nut while removing the plug f...

Page 32: ...re through the plug and tighten the screws to 4 5 Nm Note The keyboard is an intrinsically safe device Refer to the control drawings and relevant installation requirements For proper electrical termin...

Page 33: ...4 33 3 3 8 Mounting the Scanner Holder to the AG1 Housing Required Installation Tools Size 3 hex wrench Safety gloves All tools should be torque controlled if a torque is specified Figure 3 3 548268 s...

Page 34: ...Use a hex key to put the first screw with lock washer and sealing washer through the drilled hole on the right side of the AG1 housing 5 Press the scanner holder against the housing from the outside...

Page 35: ...VisuNet GXP Mechanical Installation 2020 04 35 Follow the same steps to mount the holder bracket AG1 IDMx61 B N0 for the IDM base station 548395 to the AG1 housing...

Page 36: ...2020 04 36 VisuNet GXP Mechanical Installation Figure 3 4 Technical drawing dimensions with scanner holder...

Page 37: ...equired Components S3 or S4 Interface thin client PC unit DATL IDM DB S XX00 N0 CBL IDMx60 D J1 S S18 N0 or CBL IDMx60 D J1 S C38 N0 IDM Z1 160 D 1D J1 IDM 160 D 1D J1 IDM Z1 260 D 2D J1 S1 N N0 or ID...

Page 38: ...screws Safety gloves All tools should be torque controlled if a torque is specified Connector cable DATL IDM DB S XX00 N0 Figure 3 6 Connector cable for wired 1 D scanner IDM Z1 160 D 1D J1 S S3 Inter...

Page 39: ...stalling the cable DATL IDM DB S XX00 N0 1 Open the AG1 housing See chapter 3 3 5 2 Remove the plug at the bottom right side of the housing by holding the screw steady from below with a screwdriver wh...

Page 40: ...2020 04 40 VisuNet GXP Mechanical Installation 3 Guide the open wire end of the cable DATL IDM DB S XX00 N0 through the hole 4 Place the M16 counter nut over the end of the cable...

Page 41: ...ical Installation 2020 04 41 5 Pull the socket into the housing and tighten it with the M16 counter nut Tighten the nut with a torque of 5 Nm 6 Protect the cable from mechanical damage by fastening it...

Page 42: ...le Terminal Signal Name Direction Assignment Color coding Pin M12 con nector Xx 1 Vcc Supply Vcc green 1 Xx 2 GND Supply GND brown 3 Xx 3 Xx 4 Xx 5 Xx 6 RxD I TxD white 4 Xx 7 Xx 8 TCU Cable Terminal...

Page 43: ...eing dismantled Coded Plug and Socket Warning External equipotential bonding The housing must be provided with external equipotential bonding The equipotential bonding conductor must have a minimum cr...

Page 44: ...t least three minutes then open the Ex e terminal compartment X1 4 Open terminals 1 and 2 in terminal compartment X1 5 Open the cable gland and disconnect the supply voltage cable 6 Loosen all other c...

Page 45: ...allation 2020 04 45 11 Remove the VisuNet EX1 from the AG1 housing Be sure to wear safety gloves to protect your hands Warning Risk of damage When setting the VisuNet EX1 down do not rest the EX1 on t...

Page 46: ...r Phillips head screwdriver Cable gland installation tool Tools for preparing cables wire stripper crimp tool and wire end ferrules Ratchet strap or preferably a second person to help you Socket wrenc...

Page 47: ...er to the front plate of the VisuNet GXP or to the connection surface of the AG1 housing If necessary clean the surfaces with methylated spirit or cold cleaner before installing the VisuNet GXP 5 Whil...

Page 48: ...power supply 2 Check the functions of the VisuNet RM PC e g the display external keyboard and mouse 3 Switch on the machine or plant 4 Check the functions of the machine or plant V V GND GND VCC D D G...

Page 49: ...ocket wrench for mounting nuts Appropriate tools 6 5 mm drill size for creating the cutout All tools should be torque controlled if a torque is specified If the panel mount option S2 is chosen no addi...

Page 50: ...Use the drilling pattern below to drill holes into the surface in which the panel is to be mounted Use the included bolts to fasten the panel into the wall Tighten all bolts with a torque of 4 Nm Figu...

Page 51: ...nd the monitor is recessed into the installation surface This mounting must be done from the back of the housing and the fitting is kept inside the surface of the wall The cutout dimensions and stud l...

Page 52: ...red Installation Tools 5 mm hex wrench for attaching the wall bracket screws to the AG XX00 housing Loctite Threadlocker Blue 243 Cable gland installation tool Size 8 socket wrench for ground bolt All...

Page 53: ...tuds into the AG1 back wall where indicated in the image below 3 Close the AG1 housing 4 Install the wall bracket to the AG1 housing with the included M8 screws and lock washers 5 Install the assemble...

Page 54: ...h 1 D and 2 D hand held reader for Zone 1 21 548333 CBL IDMx60 D J1 S S18 N0 Cable for connecting IDMx Z1 60 D barcode readers to the VisuNet GXP Length 1 8 m 548334 CBL IDMx60 D J1 S C38 N0 Cable for...

Page 55: ...em when the approved values of Voc or Uo and Isc or Io for the associated apparatus are less than or equal to Vmax Ui and Imax Ii for the non incendive apparatus and the approved values of Ca Co and L...

Page 56: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 5945C...

Reviews: