Power Supply PS1000-A6-24.20.R
Application Notes
20
21
-1
1
37
Figure 25.3 60A peak current for 12ms , typ. (3x the nominal current)
Note
The DC-OK relay triggers when the voltage dips below 22Vdc for longer than 1ms.
Peak current voltage dips Typically from 24V to 16 at 40A for 50ms, resistive load
Typically from 24V to 21V at 100A for 2ms, resistive load
Typically from 24V to 16.5V at 100A for 5ms, resistive load