Power Supply PS1000-A6-24.20.R
EMC
20
21
-1
1
27
18
EMC
The EMC behavior of the device is designed for applications in industrial environment
as well as in residential, commercial and light industry environments.
EMC Immunity
According to generic standards: EN 61000-6-1, and EN 61000-6-2.
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3
80MHz-2.7GHz
20V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L
→
N
L
→
PE, N
→
PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5
+
→
–
+ / –
→
PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on signals EN 61000-4-5
DC-OK signal
→
PE
1kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
20V
Criterion A
Mains voltage dips
EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion C
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11 0% of 200Vac (=0V)
5000ms
Criterion C
Voltage sags
SEMI F47 0706 80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)
1000ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Powerful transients
VDE 0160
Over entire load range
750V, 0.3ms
Criterion A
Criterion A
The device shows normal operation behavior within the defined limits.
Criterion C
Temporary loss of function is possible. The device may shut-down and restarts by itself.
No damage or hazards for the power supply will occur.
EMC Emission
According to the generic standards EN 61000-6-3 and EN 61000-6-4.
Conducted emission input lines
EN 55011, EN 55015, EN 55022,
FCC Part 15, CISPR 11, CISPR 22
Class B
Conducted emission output lines IEC/CISPR 16-1-2,
IEC/CISPR 16-2-1
5dB higher than average limits for
DC power port according
EN 61000-6-3
1
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current (PFC)
EN 61000-3-2
Class A equipment: fulfilled
Class C equipment: fulfilled in the
load range from 8 to 24A
Voltage fluctuations, flicker
EN 61000-3-3
Fulfilled, tested with constant current
loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired
operation.
1
Restrictions apply for applications in residential, commercial and light-industrial environments, where local DC power networks
according to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications.