Power Supply PS1000-A6-24.20.R
Input Inrush Current
7
Input Inrush Current
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds
after switch-on.
Figure 7.1
Typical turn-on behavior at nominal load and 25°C ambient
AC 100V
AC 120V
AC 230V
Inrush current
Max.
15A
peak
12A
peak
5.5A
peak
Temperature independent
Typ.
12A
peak
10A
peak
4.5A
peak
Temperature independent
Inrush energy
Max.
1A²s
1A²s
1A²s