20
21
-1
1
42
Power Supply PS1000-A6-24.20.R
Application Notes
Figure 25.7 Parallel use to increase output power
Do not load paralleled devices with higher currents as shown in the following diagrams:
Figure 25.8 Output current vs. ambient temperature for two paralleled units
Figure 25.9 Output current vs. ambient temperature for three paralleled units
Allowed output current for two paralleled units
0
30
40
50
60
70°C
8A
16A
24A
32A
40A
48A
B
A
Ambient Temperature
A... continuous
B... short term (max. 5s)
36.6
28A
Allowed output current for three paralleled units
0
30
40
50
60
70°C
12A
24A
36A
48A
60A
72A
B
A
Ambient Temperature
A... continuous
B... short term (max. 5s)
36.6
42A