Power Supply PS1000-A6-24.10
AC Input
20
21
-1
1
9
5
AC Input
Figure 5.1
Input voltage range
AC input
Nom. AC 100-240V Suitable for TN-, TT- and IT mains networks
AC input range
Min.
85-264Vac
Continuous operation
Min.
264-300Vac
For maximal 500ms
Allowed voltage L or N to earth Max. 300Vac
Continuous according to IEC 62477-1
Input frequency
Nom. 50–60Hz
±6%
Turn-on voltage
Typ.
80Vac
Steady-state value, see Figure 5.1
Shut-down voltage
Typ.
70Vac
Steady-state value, see Figure 5.1
Typ.
55Vac
Dynamic value for maximal 250ms
External input protection
See recommendations in chapter 26.3
AC 100V
AC 120V
AC 230V
Input current
Typ.
2.60A
2.15A
1.13A
At 24V, 10A, see Figure 5.3
Power factor
1
Typ.
0.99
0.99
0.97
At 24V, 10A, see Figure 5.4
Crest factor
2
Typ.
1.5
1.5
1.65
At 24V, 10A
Start-up delay
Typ.
300ms
290ms
240ms
See Figure 5.2
Rise time
Typ.
30ms
30ms
30ms
At 24V, 10A const. current load, 0mF
load capacitance, see Figure 5.2
Typ.
75ms
75ms
75ms
at 24V, 10A const. current load, 10mF
load capacitance, see Figure 5.2
Turn-on overshoot
Max.
200mV
200mV
200mV
See Figure 5.2
External input
protection
See recommendations in chapter 26.3
1
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
2
The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Tu
rn
-o
n
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Shut
-dow
n