Power Supply PS1000-A6-24.10
DC Input
20
21
-1
1
11
6
DC Input
Figure 6.1
Wiring for DC Input
Using DC
1.
Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency
converter is not recommended and can cause a malfunction or damage the unit.
2.
Cpole to L and -pole to N.
3.
Connect the PE terminal to an earth wire or to the machine ground.
DC input
Nom. DC 110-150V
±20%
DC input range
Min.
88-180Vdc
Continuous operation
DC input current
Typ.
2.35A
At 110Vdc, at 24V, 10A
Typ.
0.84A
At 300Vdc, at 24V, 10A
Allowed Voltage L/N to Earth Max. 375Vdc
Continuous, according to IEC 62477-1
Turn-on voltage
Typ.
80Vdc
Steady state value
Shut-down voltage
Typ.
70Vdc
Steady state value
Typ.
55Vdc
Dynamic value for maximal 250ms
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N