Commissioning
The parameters are volatile and non-volatile parameters. Volatile parameters are reset to their
default setting when the system is switched off and on again.
Non-volatile parameters
Volatile parameters
Configure the R/W system using the system commands described (see chapter 7.11). "99" is
preset as the tag type.
6.4
Setting the IP address
The IP address of the IDENTControl Compact is preset to 169.254.10.12. The way in which the
IP address is modified depends on if you are using a DHCP server.
If you are
not using a DHCP server
, the IP address is manually assigned: Either select the IP
address using the rotary switch
or
start the device with the preset IP address and specify the
new IP address on the device website.
If you are
using a DHCP server
, the server assigns the IP address to the IDENTControl
Compact.
Parameter
Default setting
Value range
General
Multiplex mode
Off
On / off
Read/write head
Trigger mode
Off
On / off
Tag type
99
00 ... 99
Ethernet interface
MAC address
00:0D:81:xx:xx:xx
00:0D:81:xx:xx:xx
DHCP
Off
On / off
IP address
169.254.10.12
yyy.yyy.yyy.yyy
Standard gateway
169.254.254.1
yyy.yyy.yyy.yyy
Subnet mask
255.255.0.0
yyy.yyy.yyy.yyy
Assembly inst. Out
100d
100d ... 112d
Data hold time
50d x 10 ms
0d ... 255d x 10 ms
Parameter
Default setting
Value range
R/W head
Password mode
Off
on / off
Password
00000000
00000000 ... FFFFFFFF
Note!
We recommend using a fixed preset IP address in order to avoid system malfunctions.
Note!
The rotary switch used to select the device address is located on the underside of the
IDENTControl Compact. This rotary switch is no longer accessible once the IDENTControl
Compact is installed.