AS-i 3.0 PROFINET Gateway in Stainless Steel
Configuration of AS-i/PROFINET Gateways
31
.1.
201
4
43
10.2.2
32 bytes digital AS-i I/O data (A and B slaves)
1 = Noise
OV
0 = OK
1 = Overvoltage
EF
0 = OK
1 = Earth falut
Pok
0 = OK
1 = Periphery fault
byte 1
Cok
0 = OK
1 = ’Config Error’
S0
1 = Address ’0’ present
0 = Adresse ’0’
not
present
AAs
1 = ’Auto_Address_Assign’
not
active
0 = ’Auto_Address_Assign’ active
AAv
1 = ’Auto_Address_Available’ active
0 = ’Auto_Address_Available’
not
active
CA
0 = ’Configuration_Active’
not
active
1 = ’Configuration_Active’ active
NA
0 = ’Normal_Operation_Active’ OK
1 = ’Normal_Operation_Active’
not
OK
APF
0 =
no
APF
1 = APF
OR
0 = online
1 = offline
Modul: 32 byte digitale I/O (A+B)
Module ident number
0x80000001
Name
32 byte digitale I/O (A+B)
Details
32 bytes digital AS-i I/O data (A and B slaves)
Category
digital I/O data
Submodule:
Submodule ident number
0x00000001
Cycl. Input data
Name
data type
display as bits
length (bytes)
Sensor data
OctetString
yes
32
Cycl. output data
Name
data type
display as bits
length (bytes)
Actuator data
OctetString
yes
32
Tab. 10-7.