AS-i 3.0 PROFINET Gateway in Stainless Steel
Configuration of AS-i/PROFINET Gateways
10.2.9
12 byte command interface
10.3
Executing of command interface commands
The command interface cann be accessed via the slot 0, subslot 1, data set 7FFF
with "date set read/write". The command interface command is executed when
the data set is written. The result can be read in the same data set. This com-
mand interface has the same structure as those in the process data.
Modul: 12 bytes Cmd If
Module ident number
0x80000002
Name
12 bytes Cmd If
Details
12 bytes command interface
Category
command interface
Submodule:
Submodule ident number
0x00000001
Cycl input data
Name
data type
display as bits
length (bytes)
Command echo
unsigned8
Execution status
unsigned8
Response data
OctetString
10
Cycl. output data
Name
data type
display as bits
length (bytes)
Command
unsigned8
AS-i circuit
unsigned8
Request data
OctetString
10
Tab. 10-17.
Information!
For information about the structure and the description of the command interface, refer
to the manual "AS-i 3.0 Command Interface".