3
1
.1
.20
1
4
54
AS-i 3.0 PROFINET Gateway in Stainless Steel
Configuration of AS-i/PROFINET Gateways
10.4.2
Manufacturer specific diagnostic
AS-i flags
structure 0xA0:
circuit 1
structure 0xA1:
circuit 2
Byte
bit
message
0
0
config error
0
1
slave 0 detected
0
2
automatic addressing
not
possible
0
3
automatic addressing possible
0
4
configuration mode
0
5
no normal operation
0
6
AS-i power fail
0
7
off-line
1
0
peripheral fault
1
1
—
1
2
—
1
3
—
1
4
earth fault
1
5
overvoltage
1
6
noise
1
7
double addressing
Tab. 10-19.
List of configuration errors
structure 0xA2:
circuit 1
structure 0xA3:
circuit 2
Byte
bit
message
0
0
slave 0: config error
0
1
slave 1/1A: config error
0
2
slave 2/2A: config error
…
…
…
3
7
slave 31/31A: config error
4
0
—
Tab. 10-20.