PROFINET diagnostics
Description of the diagnostic data which are sent via the PROFINET diagnostics
channel.
10.4.1
Channel error codes
Sl
ot
chan
nel
error
type
error text
help text
0
AS-i
Mas-
ter
16
configuration error
the actual configuration found on AS-i
does not match the projected configu-
ration, or the AS-i master performs
startup operations.
17
slave 0 detected
there is an AS-i slave with zero
address
18
no auto address
assignment
automatic address assignment would
not be possible
19
auto address assi-
gnment available
as soon as an appropriate slave is
connected, its address will be auto-
matically assigned
20
configuration
mode
the AS-i master is in configuration
mode
21
no normal opera-
tion
the AS-i master is performing startup
operations
22
AS-i power fail
the AS-i power supply is insufficient
23
off-line
the AS-i master doesn't send tele-
grams on AS-i
24
peripheral fault
at least one AS-i slave reports a peri-
pheral fault, or the AS-i master per-
forms startup operations
25
earth fault
the AS-i is short-circuited to ground
26
overvoltage
the AS-i is short-circuited to an higher
potential
27
noise
the AS-i signals are noisy
28
duplicate address
at least two AS-i slaves answers on
the same address
Tab. 10-18.
AS-i Master
0:
circuit 1
1:
circuit 2